Notifications
You must be signed in to change notification settings - Fork 13
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
- Loading branch information
1 parent
e225002
commit 4be0c45
Showing
2 changed files
with
184 additions
and
182 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,183 @@ | ||
import random | ||
import socket | ||
import struct | ||
|
||
STX = '\x02' | ||
ADDR = '\x10' | ||
CMD = '\x80' | ||
CR = '\x0D' | ||
DATA_WRITE = '\x61' | ||
DATA_READ = '\x63' | ||
ESC = '\x07' | ||
ESC_STX = '\x30' | ||
ESC_CR = '\x31' | ||
ESC_ESC = '\x32' | ||
|
||
|
||
class PTC: | ||
def __init__(self, ip_address, port=502, timeout=10, fake_errors=False): | ||
self.ip_address = ip_address | ||
self.port = int(port) | ||
self.fake_errors = fake_errors | ||
|
||
self.model = None | ||
self.serial = None | ||
self.software_revision = None | ||
|
||
self.comm = socket.socket(socket.AF_INET, socket.SOCK_STREAM) | ||
self.comm.connect((self.ip_address, self.port)) # connects to the PTC | ||
self.comm.settimeout(timeout) | ||
|
||
def get_data(self): | ||
""" | ||
Gets the raw data from the ptc and returns it in a usable format. | ||
""" | ||
self.comm.sendall(self.buildRegistersQuery()) | ||
data = self.comm.recv(1024) | ||
data_flag, brd = self.breakdownReplyData(data) | ||
|
||
return data_flag, brd | ||
|
||
@staticmethod | ||
def buildRegistersQuery(): | ||
query = bytes([0x09, 0x99, # Message ID | ||
0x00, 0x00, # Unused | ||
0x00, 0x06, # Message size in bytes | ||
0x01, # Slave Address | ||
0x04, # Function Code | ||
0x00, 0x01, # The starting Register Number | ||
0x00, 0x35]) # How many to read | ||
return query | ||
|
||
def power(self, state): | ||
"""Turn the PTC on or off. | ||
Parameters | ||
---------- | ||
state : str | ||
Desired power state of the PTC, either 'on', or 'off'. | ||
""" | ||
command = [0x09, 0x99, # Message ID | ||
0x00, 0x00, # Unused | ||
0x00, 0x06, # Message size in bytes | ||
0x01, # Slave Address | ||
0x06, # Function Code | ||
0x00, 0x01] # Register Number | ||
|
||
if state.lower() == 'on': | ||
command.extend([0x00, 0x01]) | ||
elif state.lower() == 'off': | ||
command.extend([0x00, 0xff]) | ||
else: | ||
raise ValueError(f"Invalid state: {state}") | ||
|
||
self.comm.sendall(bytes(command)) | ||
self.comm.recv(1024) # Discard the echoed command | ||
|
||
def breakdownReplyData(self, rawdata): | ||
"""Take in raw ptc data, and return a dictionary. | ||
The dictionary keys are the data labels, the dictionary values are the | ||
data in floats or ints. | ||
Returns | ||
------- | ||
data_flag : bool | ||
False if data is valid, True if output could not be interpretted. | ||
data : dict | ||
Data dictionary already formatted for passing to OCS Feed. | ||
""" | ||
|
||
# Associations between keys and their location in rawData | ||
keyloc = {"Operating_State": [9, 10], | ||
"Compressor_State": [11, 12], | ||
"Warning_State": [15, 16, 13, 14], | ||
"Alarm_State": [19, 20, 17, 18], | ||
"Coolant_In_Temp": [23, 24, 21, 22], | ||
"Coolant_Out_Temp": [27, 28, 25, 26], | ||
"Oil_Temp": [31, 32, 29, 30], | ||
"Helium_Temp": [35, 36, 33, 34], | ||
"Low_Pressure": [39, 40, 37, 38], | ||
"Low_Pressure_Average": [43, 44, 41, 42], | ||
"High_Pressure": [47, 48, 45, 46], | ||
"High_Pressure_Average": [51, 52, 49, 50], | ||
"Delta_Pressure_Average": [55, 56, 53, 54], | ||
"Motor_Current": [59, 60, 57, 58], | ||
"Hours_of_Operation": [63, 64, 61, 62], | ||
"Pressure_Unit": [65, 66], | ||
"Temperature_Unit": [67, 68], | ||
"Serial_Number": [69, 70], | ||
"Model": [71, 72], | ||
"Software_Revision": [73, 74]} | ||
|
||
# Iterate through all keys and return the data in a usable format. | ||
# If there is an error in the string format, print the | ||
# error to logs, return an empty dictionary, and flag the data as bad | ||
data = {} | ||
|
||
# If fake_errors=True, then randomly output the string 'FAKE ERROR' | ||
# instead of the actual data 50% of the time | ||
if self.fake_errors: | ||
if random.random() < 0.5: | ||
rawdata = "FAKE ERROR" | ||
|
||
try: | ||
for key in keyloc.keys(): | ||
locs = keyloc[key] | ||
wkrBytes = bytes([rawdata[loc] for loc in locs]) | ||
|
||
# four different data formats to unpack | ||
# Big endian unsigned integer 16 bits | ||
if key in [ | ||
"Operating_State", | ||
"Compressor_State", | ||
"Pressure_Unit", | ||
"Temperature_Unit", | ||
"Serial_Number", | ||
]: | ||
state = struct.unpack(">H", wkrBytes)[0] | ||
# Serial number is an attribute, not publishable data | ||
if key == "Serial_Number": | ||
self.serial = state | ||
else: | ||
data[key] = state | ||
# 32bit signed integer which is actually stored as a | ||
# 32bit IEEE float (silly) | ||
elif key in ["Warning_State", "Alarm_State"]: | ||
state = int(struct.unpack(">f", wkrBytes)[0]) | ||
data[key] = state | ||
# 2 x 8-bit lookup tables. | ||
elif key in ["Model"]: | ||
model_major = struct.unpack( | ||
">B", bytes([rawdata[locs[0]]]))[0] | ||
model_minor = struct.unpack( | ||
">B", bytes([rawdata[locs[1]]]))[0] | ||
# Model is an attribute, not publishable data | ||
self.model = str(model_major) + "_" + str(model_minor) | ||
elif key in ["Software_Revision"]: | ||
version_major = struct.unpack( | ||
">B", bytes([rawdata[locs[0]]]))[0] | ||
version_minor = struct.unpack( | ||
">B", bytes([rawdata[locs[1]]]))[0] | ||
self.software_revision = str(version_major) + "." + str(version_minor) | ||
# 32 bit Big endian IEEE floating point | ||
else: | ||
data[key] = struct.unpack(">f", wkrBytes)[0] | ||
|
||
data_flag = False | ||
|
||
except BaseException: | ||
data_flag = True | ||
print("Compressor output could not be converted to numbers." | ||
f"Skipping this data block. Bad output string is {rawdata}") | ||
|
||
return data_flag, data | ||
|
||
def __del__(self): | ||
""" | ||
If the PTC class instance is destroyed, close the connection to the | ||
ptc. | ||
""" | ||
self.comm.close() |