add eaton_abm_enabled_type_info()
Browse files Browse the repository at this point in the history
Signed-off-by: DaRK AnGeL <[email protected]>
  • Loading branch information
masterwishx committed Oct 18, 2024
1 parent 77daa28 commit 92e36d1
Showing 1 changed file with 29 additions and 13 deletions.
42 changes: 29 additions & 13 deletions drivers/mge-hid.c
Original file line number Diff line number Diff line change
Expand Up @@ -231,19 +231,33 @@ static long round (LDOUBLE value)
/* Used to store internally if ABM is enabled or not */
static const char *eaton_abm_enabled_fun(double value)
{
advanced_battery_monitoring = value;
advanced_battery_monitoring = value;

if (advanced_battery_monitoring == ABM_ENABLED_TYPE)
{
upsdebugx(2, "ABM is %s", (advanced_battery_monitoring == 4) ? "enabled" : "disabled");
}
else
upsdebugx(2, "ABM is %s", (advanced_battery_monitoring == 1) ? "enabled" : "disabled");
upsdebugx(2, "ABM is %s", (advanced_battery_monitoring==1)?"enabled":"disabled");

/* Return NULL, not to get the value published! */
return NULL;
}

/* Used to store internally if ABM is enabled or not */
static const char *eaton_abm_enabled_type_fun(double value)
{
advanced_battery_monitoring = value;

if (advanced_battery_type == ABM_CHARGER_NO_TYPE)
advanced_battery_type = ABM_CHARGER_TYPE;

upsdebugx(2, "ABM is %s", (advanced_battery_monitoring == 4) ? "enabled" : "disabled");

/* Return NULL, not to get the value published! */
return NULL;
}

static info_lkp_t eaton_abm_enabled_type_info[] = {
{ 0, "dummy", eaton_abm_enabled_type_fun, NULL },
{ 0, NULL, NULL, NULL }
};

static info_lkp_t eaton_abm_enabled_info[] = {
{ 0, "dummy", eaton_abm_enabled_fun, NULL },
{ 0, NULL, NULL, NULL }
Expand Down Expand Up @@ -281,7 +295,8 @@ static const char *eaton_abm_status_fun(double value)

upsdebugx(2, "ABM numeric status: %i", (int)value);

if (advanced_battery_monitoring == ABM_ENABLED_TYPE)
/* if we have battery.charger.type for 9E Models and others */
if (advanced_battery_type == ABM_CHARGER_TYPE)
{
switch ((long)value)
{
Expand Down Expand Up @@ -347,15 +362,15 @@ static const char *eaton_abm_charger_type_fun(double value)
{
if (value == ABM_ENABLED_TYPE)
{
/* Set ABM flag for battery.charger.type */
/* Set ABM flag for battery.charger.type */
advanced_battery_monitoring == ABM_ENABLED_TYPE;
upsdebugx(2, "ABM numeric status: %i", (int)value);

return "ABM";
}

// Handle the case when value is not equal to ABM_ENABLED_TYPE
return NULL; // or some other appropriate action
return NULL; // or some other appropriate action
};

static info_lkp_t eaton_charger_type_info[] = {
Expand All @@ -375,7 +390,8 @@ static const char *eaton_abm_chrg_dischrg_fun(double value)
if (advanced_battery_monitoring == ABM_DISABLED)
return NULL;

if (advanced_battery_monitoring == ABM_ENABLED_TYPE)
/* if we have battery.charger.type for 9E Models and others */
if (advanced_battery_type == ABM_CHARGER_TYPE)
{
switch ((long)value)
{
Expand Down Expand Up @@ -1557,7 +1573,7 @@ static hid_info_t mge_hid2nut[] =
{ "battery.charger.type", 0, 0, "UPS.BatterySystem.Charger.ChargerType", NULL, "%.0f", HU_FLAG_QUICK_POLL, eaton_charger_type_info },
{ "battery.charger.status", 0, 0, "UPS.BatterySystem.Charger.ABMEnable", NULL, "%.0f", HU_FLAG_QUICK_POLL, eaton_abm_enabled_info },
/* Same as above but for 9E Models that using ChargerType instead and other units that has ABM when .ChargerType=4 */
{ "battery.charger.status", 0, 0, "UPS.BatterySystem.Charger.ChargerType", NULL, "%.0f", HU_FLAG_QUICK_POLL, eaton_abm_enabled_info },
{ "battery.charger.status", 0, 0, "UPS.BatterySystem.Charger.ChargerType", NULL, "%.0f", HU_FLAG_QUICK_POLL, eaton_abm_enabled_type_info },
/* Same as the one above, but for legacy units */
/* Refer to Note 1 (This point will need more clarification!)
{ "battery.charger.status", 0, 0, "UPS.BatterySystem.Charger.PresentStatus.Used", NULL, "%.0f", HU_FLAG_QUICK_POLL, eaton_abm_enabled_legacy_info }, */
Expand Down