-
-
Notifications
You must be signed in to change notification settings - Fork 350
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
Merge pull request #2618 from jimklimov/man-clone
Add man page for `clone-outlet` driver
- Loading branch information
Showing
8 changed files
with
456 additions
and
75 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,197 @@ | ||
CLONE-OUTLET(8) | ||
=============== | ||
|
||
NAME | ||
---- | ||
|
||
clone-outlet - clone an UPS, treating its outlet as if it were an UPS (monitoring only) | ||
|
||
SYNOPSIS | ||
-------- | ||
|
||
*clone-outlet* -h | ||
|
||
*clone-outlet* -a 'UPS_NAME' ['OPTIONS'] | ||
|
||
NOTE: This man page only documents the specific features of the | ||
clone-outlet driver. For information about the core driver, see | ||
linkman:nutupsdrv[8]. | ||
|
||
DESCRIPTION | ||
----------- | ||
|
||
This driver, which sits on top of another driver socket, allows users to group | ||
clients to a particular outlet of a device and deal with this output as if it | ||
were a normal UPS. Unlike the linkman:clone[8] driver or linkman:dummy-ups[8] | ||
in repeater mode, this driver represents a read-only device for monitoring and | ||
shutdowns (it does not accept setting any values or sending instant commands | ||
during run time). | ||
|
||
Unlike linkman:dummy-ups[8], this driver does not require a running `upsd` | ||
data server nor use the networked NUT protocol to talk to the "real" driver | ||
(which may be remote in case of `dummy-ups` repeater mode). | ||
|
||
This driver does not create a completely new virtual device, but replaces or | ||
extends some of the original readings reported by the "real" driver using | ||
information from the specified outlet, and relays all other readings as they | ||
were. | ||
|
||
Remote clients like `upsmon` can `MONITOR` the device entry presented by the | ||
data server with this driver (and the "real" driver) running and published. | ||
|
||
A larger deployment with one or more lower-priority devices collected on a | ||
manageable outlet of an UPS or ePDU would likely see several drivers set | ||
up on the system actually capable of interactions with the UPS and running | ||
the NUT data server linkman:upsd[8] (and likely powered by another outlet): | ||
|
||
* a "real" driver talking to the UPS; | ||
* a `clone` driver talking to the "real" driver and issuing outlet power-off | ||
(or power-cycle) based on relatively high thresholds for remaining battery | ||
charge and/or runtime of the actual UPS (or explicit instant commands), | ||
with such operations first setting the respective timers for the outlet | ||
on the "real" driver, and the "FSD" flag among states of the virtual UPS | ||
status; | ||
* possibly a `clone-outlet` driver which is read-only and interprets the | ||
outlet timer values as triggers for "FSD" or "OFF" flags reported among | ||
states of the virtual UPS status. | ||
|
||
With this approach, the lower-priority systems collected on such outlet | ||
would run the NUT linkman:upsmon[8] client to `MONITOR` the virtual UPS | ||
presented by the read-only `clone-outlet` driver and shut down as soon as | ||
the "FSD" flag is raised (fairly early, based on charge and/or runtime | ||
thresholds configured for that driver) allowing the higher-priority devices | ||
(likely including the NUT server) to enjoy a longer on-battery life. | ||
|
||
The `clone` driver responsible for outlet power state changes would not | ||
normally be monitored directly (e.g. to avoid unfortunate direct shutdown | ||
requests from those clients), although it can be (instead of `clone-outlet`) | ||
in sufficiently trusted networks. | ||
|
||
EXTRA ARGUMENTS | ||
--------------- | ||
|
||
This driver supports the following settings: | ||
|
||
*port*='drivername-devicename':: | ||
Required. The standard NUT driver `port` setting, here it provides the name | ||
of the local Unix socket (or named Windows pipe) for connection to the "real" | ||
driver. | ||
|
||
*prefix*='outlet.N':: | ||
Required. Specify the outlet prefix as known on the original driver. | ||
The subset of data points reported by the "real" UPS driver for the actual device | ||
on this prefix would be reported as data points of the virtual UPS maintained by | ||
this driver. | ||
|
||
IMPLEMENTATION | ||
-------------- | ||
|
||
The port specification in the linkman:ups.conf[5] should reference the | ||
local driver socket (or Windows named pipe) that the "real" UPS driver | ||
is using. For example: | ||
|
||
------ | ||
[realups] | ||
driver = usbhid-ups | ||
port = auto | ||
|
||
[clone-outlet-1] | ||
driver = clone-outlet | ||
port = usbhid-ups-realups | ||
prefix = outlet.1 | ||
desc = "Outlet 1 of the Real UPS" | ||
[...] | ||
------ | ||
|
||
The driver internally interprets "real" driver's information about shutdown | ||
delay and shutdown timer, whole UPS status and this outlet's status, and | ||
relays other data points as they were. | ||
|
||
If the outlet supports and reports a delayed power-off, the virtual UPS would | ||
issue an FSD via `ups.status` for its clients to shut down safely. | ||
|
||
In more detail: | ||
|
||
Given the (required) `prefix` value such as `outlet.1`, the driver would | ||
specifically keep track of `<prefix>.status`, `<prefix>.delay.shutdown`, | ||
and `<prefix>.timer.shutdown` data points reported by the "real" driver. | ||
Numeric values of the `*.shutdown` readings would be noted by this driver, | ||
and the boolean outlet status ("off" or otherwise) will be remembered. | ||
These values will also be re-published by this driver "as is". | ||
|
||
The `ups.status` from the "real" driver would be remembered, but not | ||
re-published by this driver immediately. Instead, it would be published | ||
during regular "update info" loop cycles either: | ||
|
||
* with the "OFF" state added (if `<prefix>.status` indicates the outlet | ||
is "off"), | ||
* or with the "FSD" state prepended (if `<prefix>.timer.shutdown` is | ||
non-negative and does not exceed the `<prefix>.delay.shutdown` value), | ||
* or "as is" if the outlet power state is "not critical". | ||
|
||
|
||
IMPORTANT | ||
--------- | ||
|
||
Unlike a real UPS, you should *not* configure a upsmon primary mode for this | ||
driver. When a upsmon primary sees the OB LB flags and tells the upsd server | ||
it is OK to initiate the shutdown sequence, the server will latch the FSD | ||
status and it will not be possible to restart the systems connected without | ||
restarting the upsd server. | ||
|
||
This will be a problem if the power returns after the clone UPS initiated | ||
the shutdown sequence on it's outlet, but returns before the real UPS begins | ||
shutting down. The solution is in the clone driver, that will insert the | ||
FSD flag if needed without the help of a upsmon primary. | ||
|
||
CAVEATS | ||
------- | ||
|
||
The clone UPS will follow the status on the real UPS driver. You can only | ||
make the clone UPS shutdown earlier than the real UPS driver, not later. | ||
If the real UPS driver initiates a shutdown, the clone-outlet UPS driver | ||
will immediately follow. | ||
|
||
Be aware that the commands to shutdown/restart an outlet on the real UPS | ||
drivers are not affected, so if you tell the real UPS driver to shutdown | ||
the outlet of the clone UPS driver immediately, your clients will lose | ||
power without warning. A delayed outlet power-off should propagate as FSD, | ||
and the delay should be sufficiently long to allow for client shutdowns. | ||
|
||
If you use service management frameworks like systemd or SMF to manage the | ||
dependencies between driver instances and other units, then you may have | ||
to set up special dependencies (e.g. with systemd "drop-in" snippet files) | ||
to queue your `clone` drivers to start after the "real" device drivers. | ||
|
||
////////////////////////////////////// | ||
TODO later: declare the driver as "optional", see | ||
https://github.com/networkupstools/nut/issues/1389 | ||
////////////////////////////////////// | ||
|
||
AUTHOR | ||
------ | ||
|
||
Arjen de Korte <[email protected]> | ||
|
||
SEE ALSO | ||
-------- | ||
|
||
linkman:upscmd[1], | ||
linkman:upsrw[1], | ||
linkman:ups.conf[5], | ||
linkman:clone[8], | ||
linkman:nutupsdrv[8] | ||
|
||
Dummy driver: | ||
~~~~~~~~~~~~~ | ||
|
||
The "repeater" mode of 'dummy-ups' driver is in some ways similar to the | ||
'clone' and 'clone-outlet' drivers, by relaying information from a locally | ||
or remotely running "real" device driver (and NUT data server). | ||
|
||
linkman:dummy-ups[8] | ||
|
||
Internet Resources: | ||
~~~~~~~~~~~~~~~~~~~ | ||
|
||
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/ |
Oops, something went wrong.