Expand Up @@ -228,12 +228,13 @@ Thermal comfort directly affects productivity
- **Vertical Projection = Window (Shade) Width ÷ tan(HSA)**
- ![[./Attachments/2024 09 16 week 3 slides v1.pdf#page=48&rect=75,4,743,538|p.48]]

![[../../../../32N Sunpath Chart|32N Sunpath Chart]]

> [!abstract]- Lab 2
>
> 1. Using the 32N Sunpath Chart available in the Week 3 module find the solar Altitude (in degrees) in March at the 17th hour. (Note that the time is in 24 hour format). Enter the value as an integer, do not write units in your answer.
>
> ![[../../../../32N Sunpath Chart|32N Sunpath Chart]]
> 12.4392
>
> 2. Using the 32N Sunpath Chart available in the Week 3 module find the solar Altitude (in degrees) in January at the 15th hour. (Note that the time is in 24 hour format). Enter the value as an integer, do not write units in your answer.
Expand Down Expand Up @@ -641,6 +642,8 @@ Cooling Loads
- 1 kWh = 1000 Wh
- **1 $/kWh = 1/1000 $/Wh**

![[../../../../Solar Insolation|Solar Insolation]]

> [!yellow]- HD / CD Calculator
>
> ```
Expand Down Expand Up @@ -779,7 +782,9 @@ Cooling Loads
HVAC Distribution
- Pressure in ducts measured in Pascal or inches of water
- 1 inch of water = 248.84 Pa
- Diameter at each section of duct, Circular vs. Rectangular vs. Rectangular With Insulation
- Flow Efficiency
- Circular > Oval | Elliptical > Square > Rectangular
- Diameter at each section of duct
- ==Critical Path: Duct Size and Shape== [[./Attachments/2024+10+22+week+8+slides+v3 2024-10-22 14_37_23.pdf#page=31&selection=0,34,0,34|(p.31)]]
- 2in of insulation on each surface
- Turning radius is usually twice the duct diameter
Expand Down Expand Up @@ -807,12 +812,15 @@ HVAC Distribution
- ∆T = BPT - Design Dry Bulb Winter
- V_sum (cfm) = Loads (ton) × V/ton
- V/ton
- Assume V/ton = 400 cfm/ton
- Assume V/ton = 400 (cfm/ton)
- 54 (L/s/kW)
- q_1ton (Btu/h) = V/ton × Heat Capacity of Air (Btu·min/ft3·F·h) × ∆T
- 12000 = V/ton × 1.08 × ∆T_register
- ==Often the difference at the register is about 20°F. Due to losses along the length we can estimate the temperature difference at the air handler to be about 40% greater, 28°F== [[./Attachments/2024+10+22+week+8+slides+v3 2024-10-22 14_37_23.pdf#page=3&selection=30,0,36,2|(p.3)]]
- V_each = V_sum ÷ number of vent openings
![[../../../../Duct Friction Chart|Duct Friction Chart]]
> [!abstract]- Lab 7
>
> 1. For a given building located in Albany, New York the winter balance point temperature is 33.5F and the winter design temperature can be found in Table B.1 (see link below).  If the building has a UAtotal = of 3,753 Btu/(hF), what volumetric flow rate of air is needed to adequately heat the building with a forced air system?  Provide your answer in cubic feet per minute as an integer. 
Expand Down Expand Up @@ -1123,7 +1131,6 @@ HVAC Distribution
#### Module 12
> [!abstract]- Lab 9
> Net Zero PV tour, sign up
> Lab due next day 10AM