Skip to content

Commit

Permalink
PUSH NOTE : ARC2047H-Building_Science_Materials_and_Construction_3.md
Browse files Browse the repository at this point in the history
  • Loading branch information
ThinkWithPbody committed Oct 16, 2024
1 parent ae5beac commit 4dc0478
Showing 1 changed file with 11 additions and 7 deletions.
Original file line number Diff line number Diff line change
Expand Up @@ -73,11 +73,6 @@ share: true
- energy & carbon



- [x] Jacob new to bambu [completion:: 2024-09-03]
- [ ] One click LCA student license application
- [x] Send demo to dad [completion:: 2024-09-03]
- [x] Readings [due:: 2024-09-04] [completion:: 2024-09-05]
[Energy+and+the+Environment+Chapter+1+-+Ristinen+Kraushaar+Brack 2024-09-03 14_49_52.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C01%5CEnergy+and+the+Environment+Chapter+1+-+Ristinen+Kraushaar+Brack%202024-09-03%2014_49_52.pdf)
[Thermal+Delight+-+chapter+1+-+Heschong 2024-09-03 14_49_32.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C01%5CThermal+Delight+-+chapter+1+-+Heschong%202024-09-03%2014_49_32.pdf)

Expand Down Expand Up @@ -327,8 +322,17 @@ Ventilation Factor = 11 - 1.5* ((11-16)/-5) = 9.5

#### Module 07

[2024+10+14+ARC2047+week+7+slides+v1 2024-10-15 14_11_29.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C07%5C2024+10+14+ARC2047+week+7+slides+v1%202024-10-15%2014_11_29.pdf)
[ARC2047+-+Cross+Ventilation%2C+Degree+Days%2C+Cost+-+Metric+Example 2024-10-15 14_11_35.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C07%5CARC2047+-+Cross+Ventilation%2C+Degree+Days%2C+Cost+-+Metric+Example%202024-10-15%2014_11_35.pdf)
[ARC2047HF+Homework+4+Solutions+-+final 2024-10-15 14_11_40.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C07%5CARC2047HF+Homework+4+Solutions+-+final%202024-10-15%2014_11_40.pdf)
[ARC2047HF+HW5+Self+Study 2024-10-15 14_11_45.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C07%5CARC2047HF+HW5+Self+Study%202024-10-15%2014_11_45.pdf)
[Week 7 study questions.pdf](file:///D:%5COneDrive%20-%20University%20of%20Toronto%5C_twp%5CDocument%5CScholar%5CUTOR%5CArchive%5C2024-09%5CARC2047H%5CFiles%5C07%5CWeek%207%20study%20questions.pdf)

> [!PDF|yellow] [[./Attachments/2024+10+14+ARC2047+week+7+slides+v1 2024-10-15 14_11_29.pdf#page=4&selection=36,0,53,28&color=yellow|2024+10+14+ARC2047+week+7+slides+v1 2024-10-15 14_11_29, p.4]]
> > qcross ventilation = V × 1.08 Btu·min/(ft3·°F·h) × ∆T q cross ventilation is in units of power (Btu/h)
**Cooling via Cross Ventilation (Natural Ventilation)**
- q_ventilation = V × (heat capacity of air) × ∆T
- q_ventilation (Btu/h) = V (cfm) × heat capacity of air (Btu·min/(ft3·°F·h)) × ∆T (°F)
- A unit of power
- Requires openings on both sides and wind perpendicular to the opening surface
- V: Volumetric flow rate (cfm cubic feet per minute)
Expand All @@ -338,7 +342,7 @@ Ventilation Factor = 11 - 1.5* ((11-16)/-5) = 9.5
- Bottleneck is the smaller of the two
- v = velocity of the wind in feet per minute
- 1 mile per hour (mph) = 88 feet per minute (fpm)
- heat capacity of air Btu·min/(ft3·°F·h) = 0.018 Btu/(ft3·°F) × 60 min/h = 1.08 Btu·min/(ft3·°F·h)
- heat capacity of air Btu·min/(ft3·°F·h) = 0.018 Btu/(ft3·°F) × 60 min/h = **1.08 Btu·min/(ft3·°F·h)**
- OR heat capacity of air (Btu/(ft3·°F)) = density (pounds per cubic ft) * specific heat of air (Btu/(lb·°F))
- ∆T is temperature difference between inside and outside air
- At least 3°F for cross ventilation to be feasible