dsian.TcPnScanner.CLI
is a command-line tool written in C#/.NET, that scans for Profinet packets on a network interface.
It listens for packets, sent from a Profinet Controller (Master) to the requested devices.
The captured/recorded devices are then exported to a TwinCAT Profinet IO Device (TF6270)
, as *.xti
-file.
The tool supports both Windows and Linux operating systems.
This is useful for virtual commissioning/digital-twin (HiL
) projects with Beckhoff TwinCAT (TF6270)
,
which is simulating the physical Profinet devices.
It's always a huge pain to gather all required GSDML
files and to add and configure the devices manually in TwinCAT
.
It captures the connected Profinet Controller
(Master) with SharpPcap
and parses the received packets.
The captured information's are then transformed into a *.xti
file, which can be imported into TwinCAT
via the Add Existing Item⦠dialog.
A typical handshake between the Controller
and dsian.TcPnScanner.CLI
looks like this:
sequenceDiagram
Controller ->> TcPnScanner: Ident Req
Note right of Controller: From Raspberr_0a:b7:47 to PN-MC_00:00:00 <br/>PN-DCP: Ident Req, Xid:0x87ee, NameOfStation:"device-a"
TcPnScanner-->>Controller: Ident OK
Note left of TcPnScanner: From be:ef:00:00:87:ee to Raspberr_0a:b7:47 <br/>PN-DCP: Ident Ok , Xid:0x87ee, NameOfStation:"device-a", IP
Controller ->> TcPnScanner: Set Req
Note right of Controller: From Raspberr_0a:b7:47 to be:ef:00:00:87:ee <br/>PN-DCP: Set Req, Xid:0x87d6, IP 192.168.1.21/255.255.255.0
TcPnScanner-->>Controller: Set OK
Note left of TcPnScanner: From be:ef:00:00:87:ee to Raspberr_0a:b7:47 <br/>PN-DCP:Set Ok , Xid:0x87d6, Response(Ok)
Controller ->> TcPnScanner: ARP
Note right of Controller: From Raspberr_0a:b7:47 to Broadcast<br/>ARP: Who has 192.168.1.21? Tell 192.168.1.253
TcPnScanner-->>Controller: ARP
Note left of TcPnScanner: From be:ef:00:00:87:ee to Raspberr_0a:b7:47<br/>ARP: 192.168.1.21 is at be:ef:00:00:87:ee
Controller ->> TcPnScanner: Connect Req
Note right of Controller: From 192.168.1.253 to 192.168.1.21 <br/>PNIO-CM: Connect request, ARBlockReq, AlarmCRBlockReq, <br/>IOCRBlockReq, IOCRBlockReq,ExpectedSubmoduleBlockReq
Install via dotnet tool install:
dotnet tool install dsian.TcPnScanner.CLI -g
outputs
You can invoke the tool using the following command: dsian.TcPnScanner.CLI
Tool 'dsian.tcpnscanner.cli' (version '0.1.0') was successfully installed.
To use dsian.TcPnScanner.CLI
, you need to have .NET6
or later installed on your machine.
You can download it from the official website: https://dotnet.microsoft.com/download.
dotnet tool update dsian.TcPnScanner.CLI -g
dotnet tool uninstall dsian.TcPnScanner.CLI -g
outputs
Tool 'dsian.tcpnscanner.cli' (version '0.1.0') was successfully uninstalled.
- After installation simply run
dsian.TcPnScanner.CLI
- It will ask for a capturing device:
The following devices are available on this machine: ---------------------------------------------------- 0) \Device\NPF_{00000000-1234-CDEF-A603-392E759CB82A} Bluetooth Device (Personal Area Network) #2 1) \Device\NPF_{00000001-5678-1234-BFB0-E2A6A36CE73D} Intel(R) Wi-Fi 6 AX201 160MHz 2) \Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F} TwinCAT-Intel PCI Ethernet Adapter (Gigabit) V2 3) \Device\NPF_Loopback Adapter for loopback traffic capture -- Please choose a device to capture on:
- Enter the number of the device, i.e.
2
. - Capturing starts
[16:06:46 INF] π€ Selected Capture Device '\Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}: TwinCAT-Intel PCI Ethernet Adapter (Gigabit) V2' [16:06:46 INF] Opening capture device '\Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}'... [16:06:46 INF] Listening on \Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}... [16:06:47 INF] 0 At: 14/04/2023 14:06:47:481: MAC:B827EB0AB747 -> MAC:0180C200000E TYP:Lldp LEN:240 . . .
- Finished scan for devices
[16:09:12 INF] 34 At: 14/04/2023 14:09:11:997: MAC:B827EB0AB747 -> MAC:FFFFFFFFFFFF TYP:Arp LEN:42 [16:09:12 INF] 35 At: 14/04/2023 14:09:11:998: MAC:B827EB0AB747 -> MAC:BEEF000018DD TYP:IPv4 LEN:418 [16:09:15 INF] β¨ Successfully scanned 7 device(s)!
- Outputs the generated
*.xti
-file[16:09:15 INF] π Exported devices to C:\Users\densogiaichned\AppData\Local\Temp\dsian.TcPnScanner.CLI\controller (Profinet Device).xti
See Options for more options.
This tool supports piping.
When the console output is redirected, only the generated *.xti
-file is printed to console.
In case of a exception, the error is printed to console, and the application exits with exit code > 0
.
However, if piping is enabled, you have to specify a capture-device with option -d
or -f
:
dsian.TcPnScanner.CLI | echo
β A critical error occurred!
Provide option '-d'/'--capture-device' or '-f'/'--pcap-file' if Console output is redirected
Console output is redirected / piped into echo
:
dsian.TcPnScanner.CLI -f ./samples/sample-capture.pcap | echo
outputs
<?xml version="1.0" encoding="utf-8"?>
<TcSmItem xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:xsd="http://www.w3.org/2001/XMLSchema" TcSmVersion="1" TcVersion="3.1.4024.0" ClassName="CDevEthernetProtocolPnSlaveDef" SubType="115">
<Device Id="1" DevType="115" AmsPort="65535" AmsNetId="127.0.0.1.2.1" RemoteName="">
<Name>__FILENAME__</Name>
<Image Id="1" AddrType="1" ImageType="3" SizeIn="0" SizeOut="0">
<Name>Image</Name>
</Image>
<Box Id="1" BoxType="9131">
<Name>pn-io</Name>
. . .
</Box>
<Profinet PLCPortNr="851" AddPortCount="1" />
</Device>
</TcSmItem>
Option | Required | Description |
---|---|---|
-d --capture-device |
if piping | The name of the capture device to use. |
-t --timeout |
no | Capture timeout in seconds, default 180s. |
-f --pcap-file |
no | Read from a *.pcap capture file. |
-o --out-xti-file |
no | Output directory to export the TwinCAT *.xti export file. |
-l --log-level |
no | Minimum LogEventLevel, i.e. Verbose , Debug , Information , Warning , Error , Fatal . |
--log-file |
no | Path to logfile, default %TEMP%/dsian.TcPnScanner.CLI/dsian.TcPnScanner.CLI-yyyyMMddhhmm.log |
--dump |
no | Dump captured packets to file. |
--dump-file |
no | Pcap dump file. |
-h --help |
no | Display help screen. |
--version |
no | Display version information. |
Specify the name of the capture-device to use.
It will look in the device-name
or device-description
section for a matching capture-device.
Example, following devices are available on the machine:
0) \Device\NPF_{00000000-1234-CDEF-A603-392E759CB82A} Bluetooth Device (Personal Area Network) #2
1) \Device\NPF_{00000001-5678-1234-BFB0-E2A6A36CE73D} Intel(R) Wi-Fi 6 AX201 160MHz
2) \Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F} TwinCAT-Intel PCI Ethernet Adapter (Gigabit) V2
3) \Device\NPF_Loopback Adapter for loopback traffic capture
We want to capture with device #2
:
dsian.TcPnScanner.CLI -d twincat
[13:09:17 INF] π€ Selected Capture Device '\Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}: TwinCAT-Intel PCI Ethernet Adapter (Gigabit) V2'
[13:09:17 INF] Opening capture device '\Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}'...
[13:09:17 INF] Listening on \Device\NPF_{00000002-90AB-5678-8E50-52A7B958DB2F}...
[13:09:18 INF] 0 At: 14/04/2023 11:09:18:80: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
[13:09:18 INF] 1 At: 14/04/2023 11:09:18:130: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
[13:09:19 INF] 2 At: 14/04/2023 11:09:19:250: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
You may also specify the GUID
of the device:
dsian.TcPnScanner.CLI -d 00000002-90AB
A previously captured pcap
-file can be loaded, instead of capturing live-data:
dsian.TcPnScanner.CLI -l Information -f samples/sample-capture.pcap -o samples/sample-controller.xti
This loads the file samples/sample-capture.pcap
, and replays the recieved packets:
dsian.TcPnScanner.CLI -l Information -f samples/sample-capture.pcap -o samples/sample-controller.xti
[12:48:04 INF] Opening capture device 'samples/sample-capture.pcap'...
[12:48:04 INF] Listening on samples/sample-capture.pcap...
[12:48:04 INF] 0 At: 13/04/2023 19:37:03:464: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
[12:48:04 INF] 1 At: 01/01/1970 00:00:00:0: MAC:BEEF0000B51A -> MAC:B827EB0AB747 TYP:Profinet LEN:37
[12:48:04 WRN] Ignoring packet: [EthernetPacket: SourceHardwareAddress=be:ef:00:00:b5:1a, DestinationHardwareAddress=b8:27:eb:0a:b7:47, Type=Profinet]
[12:48:04 INF] 2 At: 13/04/2023 19:37:03:864: MAC:B827EB0AB747 -> MAC:BEEF0000B51A TYP:Profinet LEN:60
[12:48:04 INF] 3 At: 01/01/1970 00:00:00:0: MAC:BEEF0000B51A -> MAC:B827EB0AB747 TYP:Profinet LEN:34
[12:48:04 WRN] Ignoring packet: [EthernetPacket: SourceHardwareAddress=be:ef:00:00:b5:1a, DestinationHardwareAddress=b8:27:eb:0a:b7:47, Type=Profinet]
[12:48:04 INF] 4 At: 13/04/2023 19:37:04:744: MAC:B827EB0AB747 -> MAC:FFFFFFFFFFFF TYP:Arp LEN:42
[12:48:04 INF] 5 At: 01/01/1970 00:00:00:0: MAC:BEEF0000B51A -> MAC:B827EB0AB747 TYP:Arp LEN:42
[12:48:04 INF] 6 At: 13/04/2023 19:37:04:745: MAC:B827EB0AB747 -> MAC:BEEF00005D5D TYP:IPv4 LEN:418
[12:48:05 INF] β¨ Successfully scanned 1 device(s)!
[12:48:05 INF] π Exported devices to D:\densogiaichned\TcPnScanner\samples\sample-controller.xti
The default LogEventLevel
is Information
, which prints only the received packets header:
dsian.TcPnScanner.CLI -l Information -f samples/sample-capture.pcap -o samples/sample-controller.xti
[12:48:04 INF] Opening capture device 'samples/sample-capture.pcap'...
[12:48:04 INF] Listening on samples/sample-capture.pcap...
[12:48:04 INF] 0 At: 13/04/2023 19:37:03:464: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
[12:48:04 INF] 1 At: 01/01/1970 00:00:00:0: MAC:BEEF0000B51A -> MAC:B827EB0AB747 TYP:Profinet LEN:37
The level Verbose
also prints out the content of a packet as Raw Hex Output
:
dsian.TcPnScanner.CLI -l Verbose -f samples/sample-capture.pcap -o samples/sample-controller.xti
[12:54:00 INF] Opening capture device 'samples/sample-capture.pcap'...
[12:54:00 INF] Listening on samples/sample-capture.pcap...
[12:54:00 INF] 0 At: 13/04/2023 19:37:03:464: MAC:B827EB0AB747 -> MAC:010ECF000000 TYP:Profinet LEN:60
[12:54:00 DBG] 0 content:
Data: ******* Raw Hex Output - length=60 bytes
Data: Segment: Bytes: Ascii:
Data: --------------------------------------------------------------------------
Data: 0000 01 0e cf 00 00 00 b8 27 eb 0a b7 47 88 92 fe fe .......' ...G....
Data: 0010 05 00 00 00 b5 1a 00 01 00 0a 02 02 00 05 70 6e ........ ......pn
Data: 0020 2d 69 6f 00 00 00 00 00 00 00 00 00 00 00 00 00 -io..... ........
Data: 0030 00 00 00 00 00 00 00 00 00 00 00 00 ........ ....
dsian.TcPnScanner.CLI 0.1.0
Copyright (c) 2023 densogiaichned
ERROR(S):
Option 'h' is unknown.
-d, --capture-device (Default: ) The name of the capture device to use.
-t, --timeout (Default: 180) Capture timeout in seconds.
-f, --pcap-file (Default: ) Read from a pcap capture file.
-o, --out-xti-file (Default: %TEMP%/$APPNAME$/$CONTROLLER$.xti) Output directory to export the TwinCAT Export file.
-l, --log-level (Default: Information) Minimum LogEventLevel
--log-file (Default: %TEMP%/$APPNAME$/$APPNAME$-.log) Path to logfile
--dump (Default: false) Dump captured packets to file.
--dump-file (Default: %TEMP%/$APPNAME$/$APPNAME$-yyyyMMddHHmmss.pcap) Pcap dump file.
--help Display this help screen.
--version Display version information.
A logfile is always written, despite having the output piped into another apllication. The default logfile location is
- Windows
%TEMP%/dsian.TcPnScanner.CLI/dsian.TcPnScanner.CLI-yyyyMMddhh.log
- Linux
/tmp/dsian.TcPnScanner.CLI/dsian.TcPnScanner.CLI-yyyyMMddhh.log
However, the logfile and loglevel can be sepcified via CLI options, see Options.
This tool uses the following open source libraries:
- SharpPcap - A cross-platform packet capture framework for the .NET environment. Packet.Net - A .NET library for working with network packets.
- CommandLineParser - A command line parsing library for .NET applications.
- Verify - A library used for snapshot testing.
- Serilog - A logging library for .NET applications.
Thanks to the developers of these libraries for their contributions to the open source community.