Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Add plant worker function to get current equipment capacity #10804

Open
wants to merge 1 commit into
base: develop
Choose a base branch
from

Conversation

rraustad
Copy link
Contributor

Pull request overview

NOTE: ENHANCEMENTS MUST FOLLOW A SUBMISSION PROCESS INCLUDING A FEATURE PROPOSAL AND DESIGN DOCUMENT PRIOR TO SUBMITTING CODE

Pull Request Author

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Title of PR should be user-synopsis style (clearly understandable in a standalone changelog context)
  • Label the PR with at least one of: Defect, Refactoring, NewFeature, Performance, and/or DoNoPublish
  • Pull requests that impact EnergyPlus code must also include unit tests to cover enhancement or defect repair
  • Author should provide a "walkthrough" of relevant code changes using a GitHub code review comment process
  • If any diffs are expected, author must demonstrate they are justified using plots and descriptions
  • If changes fix a defect, the fix should be demonstrated in plots and descriptions
  • If any defect files are updated to a more recent version, upload new versions here or on DevSupport
  • If IDD requires transition, transition source, rules, ExpandObjects, and IDFs must be updated, and add IDDChange label
  • If structural output changes, add to output rules file and add OutputChange label
  • If adding/removing any LaTeX docs or figures, update that document's CMakeLists file dependencies

Reviewer

This will not be exhaustively relevant to every PR.

  • Perform a Code Review on GitHub
  • If branch is behind develop, merge develop and build locally to check for side effects of the merge
  • If defect, verify by running develop branch and reproducing defect, then running PR and reproducing fix
  • If feature, test running new feature, try creative ways to break it
  • CI status: all green or justified
  • Check that performance is not impacted (CI Linux results include performance check)
  • Run Unit Test(s) locally
  • Check any new function arguments for performance impacts
  • Verify IDF naming conventions and styles, memos and notes and defaults
  • If new idf included, locally check the err file and other outputs

@rraustad rraustad added the Defect Includes code to repair a defect in EnergyPlus label Oct 25, 2024
@rraustad
Copy link
Contributor Author

rraustad commented Oct 25, 2024

With the new worker function the cooling tower can now meet the load.

image

Copy link
Contributor Author

@rraustad rraustad left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Walk thru

@@ -6474,6 +6474,81 @@ namespace CondenserLoopTowers {
}
}

Real64 CoolingTower::getDynamicMaxCapacity(EnergyPlusData &state)
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Tower calculations for current maximum capacity

if (this->compPtr == NULL) return this->MaxLoad;
Real64 possibleLoad = this->compPtr->getDynamicMaxCapacity(state);
return (possibleLoad == 0) ? this->MaxLoad : possibleLoad;
}
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This function will call the virtual function in PlantComponent.hh if a model does not have the override function (if that equipment's maximum capacity does not change) or will call the override function in the equipment model. If this function does not exist in an equipment model the virtual function will return 0 and MaxLoad will be used just as it is now. Otherwise the equipment model will return the current max capacity and that value will be used instead.

virtual Real64 getDynamicMaxCapacity([[maybe_unused]] EnergyPlusData &state)
{
return 0.0;
}
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Virtual function returns 0 if equipment model does not have an override function.

@@ -107,7 +107,7 @@ using HVAC::SmallLoad;

void ManagePlantLoadDistribution(EnergyPlusData &state,
PlantLocation const &plantLoc, // PlantLoop data structure Location struct
Real64 &LoopDemand,
Real64 const LoopDemand,
Copy link
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

CppCheck suggestion

@@ -3673,7 +3673,7 @@ void FindCompSPLoad(EnergyPlusData &state,

// load local variables from the data structures
CompMinLoad = this_component.MinLoad;
CompMaxLoad = this_component.MaxLoad;
CompMaxLoad = this_component.getDynamicMaxCapacity(state);
Copy link
Contributor Author

@rraustad rraustad Oct 25, 2024

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Down at line 3763 is code that will cap MyLoad if the component cannot meet the load. Calling this function provides a more accurate full load capacity for use in plant manager calculations.

    // Check bounds on MyLoad
    if (std::abs(this_component.MyLoad) > CompMaxLoad) {
        this_component.MyLoad = sign(CompMaxLoad, this_component.MyLoad);
    }

@rraustad rraustad added this to the EnergyPlus 25.1 milestone Oct 25, 2024
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
Defect Includes code to repair a defect in EnergyPlus
Projects
None yet
Development

Successfully merging this pull request may close these issues.

Allow water plant to access equipment operating capacity for plant dispatch management