Skip to content

Commit

Permalink
Merge branch 'develop' of https://github.com/NREL/EnergyPlus into NFP…
Browse files Browse the repository at this point in the history
…-Refrigerant-Migration-Decarbonization
  • Loading branch information
rraustad committed Jul 24, 2024
2 parents b8cb611 + 8c96cbb commit 274582b
Show file tree
Hide file tree
Showing 188 changed files with 10,006 additions and 8,341 deletions.
709 changes: 709 additions & 0 deletions design/FY2024/NFP-RulesetModelDescriptionPhase3.md

Large diffs are not rendered by default.

Original file line number Diff line number Diff line change
Expand Up @@ -59,7 +59,7 @@ \subsubsection{Energy budget in the foliage layer}\label{energy-budget-in-the-fo
Where $\sigma$\(_{f}\) is calculated as a function of Leaf-Area-Index (LAI):

\begin{equation}
\sigma_f = 0.9 - 0.7 \exp{-0.75 LAI }
\sigma_f = 0.9 - 0.7 \exp^{-0.75 LAI}
\end{equation}

In addition to convective and sensible heat transfer this equation accounts for both the short and longwave radiation absorbed by the vegetation, including the effects of multiple reflections. The sensible and latent heat flux terms (H\(_{f}\) and L\(_{f-}\)) are somewhat complicated and therefore discussed in some detail below.
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -326,7 +326,7 @@ \subsection{HVACTemplate:Zone:IdealLoadsAirSystem}\label{hvactemplatezoneideallo

This component can be operated with infinite or finite heating and cooling capacity. For either mode -- infinite or limited capacity -- the user can also specify on/off schedules for heating and cooling and outdoor air controls. There are also optional controls for dehumidification, humidification, economizer, and heat recovery. This component may be used in combination with other HVAC equipment serving the same zone.

This component can be thought of as an ideal unit that mixes air at the zone exhaust condition with the specified amount of outdoor air and then adds or removes heat and moisture at 100\% efficiency in order to produce a supply air stream at the specified conditions. The energy required to condition the supply air is metered and reported as \hyperref[districtheating]{DistrictHeating} and \hyperref[districtcooling]{DistrictCooling}.
This component can be thought of as an ideal unit that mixes air at the zone exhaust condition with the specified amount of outdoor air and then adds or removes heat and moisture at 100\% efficiency in order to produce a supply air stream at the specified conditions. The energy required to condition the supply air is metered and reported as \hyperref[districtheating]{DistrictHeatingWater} and \hyperref[districtcooling]{DistrictCooling}.

\subsubsection{Inputs}\label{inputs-1-022}

Expand Down Expand Up @@ -910,7 +910,7 @@ \subsubsection{Inputs}\label{inputs-4-016}

\paragraph{Field: Cooling Coil Type}\label{field-cooling-coil-type-1}

Enter the type of cooling coil. There is currently only one choices for this field, SingleSpeedDX.
Enter the type of cooling coil. There is currently only one choice for this field, SingleSpeedDX.

\paragraph{Field: Cooling Coil Availability Schedule Name}\label{field-cooling-coil-availability-schedule-name-1}

Expand Down Expand Up @@ -1156,7 +1156,7 @@ \subsubsection{Inputs}\label{inputs-5-014}

\paragraph{Field: Cooling Coil Type}\label{field-cooling-coil-type-2}

Enter the type of cooling coil. There is currently only one choices for this field, SingleSspeedDX.
Enter the type of cooling coil. There is currently only one choice for this field, SingleSpeedDX.

\paragraph{Field: Cooling Coil Availability Schedule Name}\label{field-cooling-coil-availability-schedule-name-2}

Expand All @@ -1176,7 +1176,7 @@ \subsubsection{Inputs}\label{inputs-5-014}

\paragraph{Field: Heat Pump Heating Coil Type}\label{field-heat-pump-heating-coil-type}

Enter the type of heat pump heating coil. There is currently only one choices for this field, SingleSpeedDXHeatPump.
Enter the type of heat pump heating coil. There is currently only one choice for this field, SingleSpeedDXHeatPump.

\paragraph{Field: Heat Pump Heating Coil Availability Schedule Name}\label{field-heat-pump-heating-coil-availability-schedule-name}

Expand Down Expand Up @@ -1445,7 +1445,8 @@ \subsubsection{Inputs}\label{inputs-6-011}

\paragraph{Field: Cooling Coil Type}\label{field-cooling-coil-type-3}

Enter the type of cooling coil. There is currently only one choices for this field, \hyperref[coilcoolingwatertoairheatpumpequationfit]{Coil:Cooling:WaterToAirHeatPump:EquationFit}.
Enter the type of cooling coil. At the present time, there is currently only one choice for this field:
\hyperref[coilcoolingwatertoairheatpumpequationfit]{Coil:Cooling:WaterToAirHeatPump:EquationFit}

\paragraph{Field: Cooling Coil Gross Rated Total Capacity}\label{field-cooling-coil-gross-rated-total-capacity-2}

Expand All @@ -1461,7 +1462,8 @@ \subsubsection{Inputs}\label{inputs-6-011}

\paragraph{Field: Heat Pump Heating Coil Type}\label{field-heat-pump-heating-coil-type-1}

Enter the type of heat pump heating coil. There is currently only one choices for this field, \hyperref[coilheatingwatertoairheatpumpequationfit]{Coil:Heating:WaterToAirHeatPump:EquationFit}.
Enter the type of heat pump heating coil. There is currently only one choice for this field:
\hyperref[coilheatingwatertoairheatpumpequationfit]{Coil:Heating:WaterToAirHeatPump:EquationFit}.

\paragraph{Field: Heat Pump Heating Coil Gross Rated Capacity}\label{field-heat-pump-heating-coil-gross-rated-capacity-1}

Expand Down Expand Up @@ -3654,9 +3656,7 @@ \subsubsection{Inputs}\label{inputs-16-004}

\paragraph{Field: Cooling Coil Type}\label{field-cooling-coil-type-6}

Enter the type of cooling coil. There is currently only one choices for this field,

SingleSpeedDX. Future versions may have additional cooling coil types.
Enter the type of cooling coil. There is currently only one choice for this field, SingleSpeedDX. Future versions may have additional cooling coil types.

\paragraph{Field: Cooling Coil Availability Schedule Name}\label{field-cooling-coil-availability-schedule-name-5}

Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -2719,7 +2719,7 @@ \subsubsection{Outputs}\label{outputs-gndSrfs}

This is an average surface reflectance of multiple ground surfaces viewed by an exterior surface for each time step. If there is only one ground surface specified in a given \textit{SurfaceProperty:GroundSurfaces} object, then the average surface reflectance will be the same as the specified ground surface reflectance. This output variable is not generated when all ground surface reflectance schedule name fields are blank.

\subsection{References}\label{references-gnd-srfs}
\subsubsection{References}\label{references-gnd-srfs}

Bill Marion. 2018. Ground Albedo Measurements and Modeling. Bifacial PV Workshop Lakewood, Colorado. September 11, 2018.
NREL/PR-5K00-72589. https://www.nrel.gov/docs/fy20osti/72589.pdf
Expand Down
26 changes: 17 additions & 9 deletions doc/input-output-reference/src/overview/group-design-objects.tex
Original file line number Diff line number Diff line change
Expand Up @@ -752,7 +752,7 @@ \subsubsection{Component Sizing Output}\label{component-sizing-output}
The complete list of objects that have autosized fields is shown in the following table. Note that spaces may be inserted in object names to facilitate readability.

% table 23
\begin{longtable}[c]{p{3.02in}p{2.97in}}
\begin{longtable}[c]{p{3.3in}p{3.3in}}
\caption{Complete list of Objects with autosized Fields \label{table:complete-list-of-objects-with-autosized}} \tabularnewline
\toprule
Object Name & Object Name \tabularnewline
Expand All @@ -767,17 +767,22 @@ \subsubsection{Component Sizing Output}\label{component-sizing-output}

AirConditioner:VariableRefrigerantFlow & AirLoopHVAC \tabularnewline
AirLoopHVAC:Unitary:Furnace:HeatCool & AirLoopHVAC:Unitary:Furnace:HeatOnly \tabularnewline
AirLoopHVAC:UnitaryHeatCool & AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass \tabularnewline
AirLoopHVAC:UnitaryHeatCool & \tabularnewline
AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass & \tabularnewline
AirLoopHVAC:UnitaryHeatOnly & AirLoopHVAC:UnitaryHeatPump:AirToAir \tabularnewline
AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed & AirLoopHVAC:UnitaryHeatPump:WaterToAir \tabularnewline
AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed & \tabularnewline
AirLoopHVAC:UnitaryHeatPump:WaterToAir & \tabularnewline
AirLoopHVAC:UnitarySystem & AirTerminal:DualDuct:ConstantVolume \tabularnewline
AirTerminal:DualDuct:VAV & AirTerminal:DualDuct:VAV:OutdoorAir \tabularnewline
AirTerminal:SingleDuct:ConstantVolume:CooledBeam & AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction \tabularnewline
AirTerminal:SingleDuct:ConstantVolume:CooledBeam & \tabularnewline
AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction & \tabularnewline
AirTerminal:SingleDuct:ConstantVolume:Reheat & AirTerminal:SingleDuct:ParallelPIU:Reheat \tabularnewline
AirTerminal:SingleDuct:SeriesPIU:Reheat & AirTerminal:SingleDuct:ConstantVolume:NoReheat \tabularnewline
AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat & AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat \tabularnewline
AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat & \tabularnewline
& AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat \tabularnewline
AirTerminal:SingleDuct:VAV:NoReheat & AirTerminal:SingleDuct:VAV:Reheat \tabularnewline
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan & Boiler:HotWater \tabularnewline
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan & \tabularnewline
& Boiler:HotWater \tabularnewline
Boiler:Steam & Branch \tabularnewline
Chiller:Absorption & Chiller:Absorption:Indirect \tabularnewline
Chiller:CombustionTurbine & Chiller:ConstantCOP \tabularnewline
Expand All @@ -789,13 +794,15 @@ \subsubsection{Component Sizing Output}\label{component-sizing-output}
Coil:Cooling:DX:TwoSpeed & Coil:Cooling:DX:VariableRefrigerantFlow \tabularnewline
Coil:Cooling:DX:VariableSpeed & Coil:Cooling:Water \tabularnewline
Coil:Cooling:Water:DetailedGeometry & Coil:Cooling:WaterToAirHeatPump:EquationFit \tabularnewline
Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit & Coil:Heating:DX:MultiSpeed \tabularnewline
Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit & \tabularnewline
& Coil:Heating:DX:MultiSpeed \tabularnewline
Coil:Heating:DX:SingleSpeed & Coil:Heating:DX:VariableRefrigerantFlow \tabularnewline
Coil:Heating:DX:VariableSpeed & Coil:Heating:Electric \tabularnewline
Coil:Heating:Electric:MultiStage & Coil:Heating:Fuel \tabularnewline
Coil:Heating:Gas:MultiStage & Coil:Heating:Steam \tabularnewline
Coil:Heating:Water & Coil:Heating:WaterToAirHeatPump:EquationFit \tabularnewline
Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit & CoilPerformance:DX:Cooling \tabularnewline
Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit & \tabularnewline
& CoilPerformance:DX:Cooling \tabularnewline
CondenserLoop & Controller:OutdoorAir \tabularnewline
Controller:WaterCoil & CoolingTower:SingleSpeed \tabularnewline
CoolingTower:TwoSpeed & CoolingTower:VariableSpeed \tabularnewline
Expand All @@ -811,7 +818,8 @@ \subsubsection{Component Sizing Output}\label{component-sizing-output}
HVACTemplate:Plant:Tower & HVACTemplate:System:ConstantVolume \tabularnewline
HVACTemplate:System:DedicatedOutdoorAir & HVACTemplate:System:DualDuct \tabularnewline
HVACTemplate:System:PackagedVAV & HVACTemplate:System:Unitary \tabularnewline
HVACTemplate:System:UnitaryHeatPump:AirToAir & HVACTemplate:System:UnitarySystem \tabularnewline
HVACTemplate:System:UnitaryHeatPump:AirToAir & \tabularnewline
& HVACTemplate:System:UnitarySystem \tabularnewline
HVACTemplate:System:VAV & HVACTemplate:System:VRF \tabularnewline
HVACTemplate:Zone:BaseboardHeat & HVACTemplate:Zone:ConstantVolume \tabularnewline
HVACTemplate:Zone:DualDuct & HVACTemplate:Zone:FanCoil \tabularnewline
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -4451,7 +4451,7 @@ \subsubsection{Inputs}\label{inputs-20-000}

\paragraph{Field: Surface Name}\label{field-surface-name-001}

This field is the name of a surface that defines the location and geometry of the array.
This field is the name of a surface that defines the location and geometry of the array. Array tilt, azimuth, and gross area are taken from the referenced building surface or shading surface. This will define the orientation of the solar panel for the detailed models and also the area of the solar panel for the simple model.

\paragraph{Field: Photovoltaic Performance Object Type}\label{field-photovoltaic-performance-object-type}

Expand Down
30 changes: 16 additions & 14 deletions doc/input-output-reference/src/overview/group-heat-recovery.tex
Original file line number Diff line number Diff line change
Expand Up @@ -264,12 +264,6 @@ \subsubsection{Inputs}\label{inputs-1-019}

The latent heat exchange effectiveness at the \emph{heating} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 100\% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.

\paragraph{Field: Sensible Effectiveness at 75\% Heating Air Flow}\label{field-sensible-effectiveness-at-75-heating-air-flow}

The sensible heat exchange effectiveness at the \emph{heating} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 75\% of the nominal supply air flow rate. The default value for this field is 0.

\paragraph{Field: Latent Effectiveness at 75\% Heating Air Flow}\label{field-latent-effectiveness-at-75-heating-air-flow}

The latent heat exchange effectiveness at the \emph{heating} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 75\% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.

\paragraph{Field: Sensible Effectiveness at 100\% Cooling Air Flow}\label{field-sensible-effectiveness-at-100-cooling-air-flow}
Expand All @@ -280,14 +274,6 @@ \subsubsection{Inputs}\label{inputs-1-019}

The latent heat exchange effectiveness at the \emph{cooling} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 100\% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.

\paragraph{Field: Sensible Effectiveness at 75\% Cooling Air Flow}\label{field-sensible-effectiveness-at-75-cooling-air-flow}

The sensible heat exchange effectiveness at the \emph{cooling} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 75\% of the nominal supply air flow rate. The default value for this field is 0.

\paragraph{Field: Latent Effectiveness at 75\% Cooling Air Flow}\label{field-latent-effectiveness-at-75-cooling-air-flow}

The latent heat exchange effectiveness at the \emph{cooling} condition defined in Table~\ref{table:operating-conditions-for-defining-heat} with both the supply and exhaust air volume flow rates equal to 75\% of the nominal supply air flow rate. Specify this value as 0.0 if the heat exchanger does not transfer latent energy. The default value for this field is 0.

\paragraph{Field: Supply Air Inlet Node Name}\label{field-supply-air-inlet-node-name-1-000}

The name of the HVAC system node from which the unit draws its supply (primary) inlet air.
Expand Down Expand Up @@ -392,6 +378,22 @@ \subsubsection{Inputs}\label{inputs-1-019}

This input denotes whether the heat exchanger unit is locked out (bypassed for plate type heat exchangers or the rotation is suspended for rotary type heat exchangers) when the air-side economizer is operating. Both the economizer and high humidity control (Ref. \hyperref[controlleroutdoorair]{Controller:OutdoorAir}) activate the heat exchanger lockout as specified by this input. The input choices are \emph{Yes} (meaning locked out) or \emph{No}. The default input for this field is Yes.

\paragraph{Field: Sensible Effectiveness of Heating Air Flow Curve Name}\label{field-sensible-effectiveness-of-heating-air-flow-curve-name-1}

This optional input allows the user to specify a curve that determines the value of the sensible effectiveness for heating. The result of the curve is multipled by the sensible effectiveness at 100\% heating (see field: \hyperref[field-sensible-effectiveness-at-100-heating-air-flow]{Sensible Effectiveness at 100\% Heating Air Flow} above).

\paragraph{Field: Latent Effectiveness of Heating Air Flow Curve Name}\label{field-latent-effectiveness-of-heating-air-flow-curve-name-1}

This optional input allows the user to specify a curve that determines the value of the latent effectiveness for heating. The result of the curve is multipled by the latent effectiveness at 100\% heating (see field: \hyperref[field-latent-effectiveness-at-100-heating-air-flow]{Latent Effectiveness at 100\% Heating Air Flow} above).

\paragraph{Field: Sensible Effectiveness of Cooling Air Flow Curve Name}\label{field-sensible-effectiveness-of-cooling-air-flow-curve-name-1}

This optional input allows the user to specify a curve that determines the value of the sensible effectiveness for cooling. The result of the curve is multipled by the sensible effectiveness at 100\% cooling (see field: \hyperref[field-sensible-effectiveness-at-100-cooling-air-flow]{Sensible Effectiveness at 100\% Cooling Air Flow} above).

\paragraph{Field: Latent Effectiveness of Cooling Air Flow Curve Name}\label{field-latent-effectiveness-of-cooling-air-flow-curve-name-1}

This optional input allows the user to specify a curve that determines the value of the latent effectiveness for cooling. The result of the curve is multipled by the latent effectiveness at 100\% cooling (see field: \hyperref[field-latent-effectiveness-at-100-cooling-air-flow]{Latent Effectiveness at 100\% Cooling Air Flow} above).

Following is an example input for this heat exchanger object:

\begin{lstlisting}
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -209,17 +209,19 @@ \subsubsection{Inputs}\label{inputs-1-021}
\item
HVAC,Sum,Humidifier Water Volume{[}m3{]}
\item
HVAC,Average,Humidifier Gas Use Rate{[}W{]}
HVAC,Average,Humidifier NaturalGas Use Rate{[}W{]}
\item
HVAC,Sum,Humidifier Gas Use Energy {[}J{]}
HVAC,Sum,Humidifier NaturalGas Use Energy {[}J{]}
\item
HVAC,Average,Humidifier NaturalGas Use Thermal Efficiency {[}{]}
\item
HVAC,Average,Humidifier Auxiliary Electricity Rate {[}W{]}
\item
HVAC,Sum,Humidifier Auxiliary Electricity Energy {[}J{]}
\item
HVAC,Meter,Humidifier:Water {[}m3{]}
\item
HVAC,Meter,Humidifier:Gas {[}J{]}
HVAC,Meter,Humidifier:NaturalGas {[}J{]}
\item
HVAC,Meter,Humidifier:Electricity {[}J{]}
\item
Expand All @@ -244,13 +246,17 @@ \subsubsection{Inputs}\label{inputs-1-021}

This output is the cubic meters of water consumed by the steam humidifier over the timestep being reported.

\paragraph{Humidifier Gas Use Rate {[}W{]}}\label{humidifier-gas-use-rate-w}
\paragraph{Humidifier NaturalGas Use Rate {[}W{]}}\label{humidifier-naturalgas-use-rate-w}

This output is the gas use rate of the gas fired steam humidifier in Watts.
This output is the natural gas use rate of the natural gas fired steam humidifier in Watts.

\paragraph{Humidifier Gas Use Energy {[}J{]}}\label{humidifier-gas-use-energy-j}
\paragraph{Humidifier NaturalGas Use Energy {[}J{]}}\label{humidifier-naturalgas-use-energy-j}

This output is the gas consumption of the gas fired steam humidifier in Joules.
This output is the natural gas consumption of the natural gas fired steam humidifier in Joules.

\paragraph{Humidifier NaturalGas Use Thermal Efficiency {[}{]}}\label{humidifier-naturalgas-use-thermal-efficiency-j}

This output is the thermal efficiency of the natural gas consumed by the natural gas fired steam humidifier.

\paragraph{Humidifier Auxiliary Electricity Rate {[}W{]}}\label{humidifier-auxiliary-electric-power-w}

Expand All @@ -264,9 +270,9 @@ \subsubsection{Inputs}\label{inputs-1-021}

This meter output contains the sum of the water consumed (in cubic meters of water during the report timestep) by all the steam humidifiers at the HVAC level in the simulation.

\paragraph{Humidifier:Gas {[}J{]}}\label{humidifiergas-j}
\paragraph{Humidifier:NaturalGas {[}J{]}}\label{humidifiernaturalgas-j}

This meter output contains the sum of the gas consumed (in Joules during the report timestep) by all the steam humidifiers at the HVAC level in the simulation.
This meter output contains the sum of the natural gas consumed (in Joules during the report timestep) by all the steam humidifiers at the HVAC level in the simulation.

\paragraph{Humidifier Storage Tank Water Volume Flow Rate {[}m3/s{]}}\label{humidifier-storage-tank-water-volume-flow-rate-m3s-1}

Expand Down
Loading

5 comments on commit 274582b

@nrel-bot-3
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

NFP-Refrigerant-Migration-Decarbonization (rraustad) - x86_64-MacOS-10.18-clang-15.0.0: OK (3538 of 3646 tests passed, 175 test warnings)

Messages:\n

  • 283 tests had: AUD diffs.
  • 279 tests had: RDD diffs.
  • 131 tests had: Table small diffs.
  • 108 tests had: Table big diffs.
  • 1 test had: MTD diffs.

Failures:\n

regression Test Summary

  • Passed: 684
  • Failed: 108

Build Badge Test Badge

@nrel-bot
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

NFP-Refrigerant-Migration-Decarbonization (rraustad) - Win64-Windows-10-VisualStudio-16: OK (2853 of 2853 tests passed, 0 test warnings)

Build Badge Test Badge

@nrel-bot-2b
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

NFP-Refrigerant-Migration-Decarbonization (rraustad) - x86_64-Linux-Ubuntu-22.04-gcc-11.4: OK (3577 of 3687 tests passed, 175 test warnings)

Messages:\n

  • 283 tests had: AUD diffs.
  • 279 tests had: RDD diffs.
  • 131 tests had: Table small diffs.
  • 108 tests had: Table big diffs.
  • 1 test had: MTD diffs.

Failures:\n

EnergyPlusFixture Test Summary

  • Passed: 1565
  • Failed: 2

regression Test Summary

  • Passed: 704
  • Failed: 108

Build Badge Test Badge

@nrel-bot-2c
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

NFP-Refrigerant-Migration-Decarbonization (rraustad) - x86_64-Linux-Ubuntu-22.04-gcc-11.4-UnitTestsCoverage-Debug: OK (2056 of 2060 tests passed, 0 test warnings)

Failures:\n

EnergyPlusFixture Test Summary

  • Passed: 1563
  • Subprocess aborted: 4

Build Badge Test Badge Coverage Badge

@nrel-bot-2
Copy link

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

NFP-Refrigerant-Migration-Decarbonization (rraustad) - x86_64-Linux-Ubuntu-22.04-gcc-11.4-IntegrationCoverage-Debug: OK (796 of 796 tests passed, 0 test warnings)

Build Badge Test Badge Coverage Badge

Please sign in to comment.