Fixed to calculate power factor correctly. Previously it would go negative for no reason.
Adjusted startup thresholds registers (not relevant to EmonESP)
Set Sag and Voltage peak detect period set to 20ms (not relevant to EmonESP)
Corrected F1-F7 registers, which are voltage & current peak, not THD (they are TDH on the ATM90E36) (not relevant to EmonESP)
Corrected N RMS calculated current address (DC, not D8) (not relevant to EmonESP)
Removed canBeNegative for regular meter so it's easy to tell when a current transformer is backwards. If one is backwards, active power calculations will be off because power factor will be off.