[HCL] PowerWalker VFI 1000 AT supported by usbhid-ups #2632
Comments
Thank you! |
By the way. |
Can you try building current NUT to test the driver from workspace? No need to replace the existing installation, although you would need to add prerequisite and tool packages... |
Just checked on clear Ubuntu 22.04 with last git version
|
For voltage, diff suggests this was among drivers impacted by #1024 and related work to fix wrong encoding of sime values. Maybe it misfires here, try adding |
Not helped 😞. By the way, I don't know what this value shows, but sometimes it changes its value. |
PowerWalker VFI 1000 AT
upsc
:upsrw
:upscmd
:My
ups.conf
:Shutdown of clients, server and UPS works. But it seems it ignores
ondelay
andoffdelay
. I tried different values for them but the result is always the same. Afterupsmon -c fsd
in/bin/upssched-cmd
invoked server starts to shutdown. After ~15 seconds timer appears on the UPS's display. After even ~10 seconds UPS shuts down outlets (timer is still on dislay). After all of that UPS continues to work with outlets turned off. And only after 2 more minutes UPS shuts down.The text was updated successfully, but these errors were encountered: