#!/bin/bash
# Check the upsmgBatteryTemperature of MGE UPS using snmp
# [email protected] 2021/02/24 - Version 0.1
function usage {
echo "Usage: $0 -H hostname -P password -w warning -c critical"
exit 0
}
function isnumber {
case $OPTARG in
[!0-9]* ) echo "Error: -$opt must be an Integer"
usage;;
esac
}
while getopts "H:P:w:c:" opt; do
case $opt in
H) THEHOST=$OPTARG;;
P) PASS=$OPTARG;;
w) isnumber
WARN=$OPTARG;;
c) isnumber
CRIT=$OPTARG;;
*) usage;;
esac
done
if [ -z "$THEHOST" ] || [ -z "$PASS" ] || [ -z "$WARN" ] || [ -z "$CRIT" ]; then
echo "Error: Required option not found"
usage
fi
if [ "$WARN" -gt "$CRIT" ]; then
echo "Error: -c must be higher than -w"
usage
fi
TEMP=$(snmpwalk -v 1 -c "$PASS" "$THEHOST" .1.3.6.1.4.1.705.1.5.7 | cut -d":" -f4 | tr -d " ")
if [ $? -eq 0 ]; then
if [ "$TEMP" -ge "$CRIT" ]; then
echo "CRITICAL Temp: ${TEMP} C"
exit 2
elif [ "$TEMP" -ge "$WARN" ] && [ "$TEMP" -lt "$CRIT" ]; then
echo "Warning: ${TEMP} C"
exit 1
else
echo "OK: ${TEMP} C"
exit 0
fi
fi