changed enabling conditions, #2293
Browse files Browse the repository at this point in the history
  • Loading branch information
JayHuLBL committed Feb 11, 2021
1 parent 2456aa9 commit 9fbb319
Showing 1 changed file with 7 additions and 5 deletions.
Original file line number Diff line number Diff line change
Expand Up @@ -11,7 +11,7 @@ block Controller "Head pressure controller"
parameter Boolean have_WSE=true
"Flag indicating if the plant has waterside economizer"
annotation (Dialog(group="Plant"));
parameter Boolean fixSpePum=true
parameter Boolean fixSpePum=false
"Flag indicating if the plant has fixed speed condenser water pumps"
annotation (Dialog(group="Plant", enable=not have_WSE));
parameter Real minChiLif=10
Expand Down Expand Up @@ -48,7 +48,7 @@ block Controller "Head pressure controller"
Buildings.Controls.OBC.CDL.Interfaces.RealInput desConWatPumSpe(
final min=0,
final max=1,
final unit="1") if not ((not have_WSE) and fixSpePum)
final unit="1") if (not have_WSE and varSpePum) or have_WSE
"Design condenser water pump speed for current stage"
annotation (Placement(transformation(extent={{-140,0},{-100,40}}),
iconTransformation(extent={{-140,-40},{-100,0}})));
Expand All @@ -72,14 +72,14 @@ block Controller "Head pressure controller"
Buildings.Controls.OBC.CDL.Interfaces.RealOutput yHeaPreConVal(
final min=0,
final max=1,
final unit="1") if not ((not have_WSE) and not fixSpePum)
final unit="1") if have_WSE or (not have_WSE and not varSpePum)
"Head pressure control valve position"
annotation (Placement(transformation(extent={{100,0},{140,40}}),
iconTransformation(extent={{100,-20},{140,20}})));
Buildings.Controls.OBC.CDL.Interfaces.RealOutput yConWatPumSpeSet(
final min=0,
final max=1,
final unit="1") if not ((not have_WSE) and fixSpePum)
final unit="1") if (not have_WSE and varSpePum) or have_WSE
"Condenser water pump speed setpoint"
annotation (Placement(transformation(extent={{100,-50},{140,-10}}),
iconTransformation(extent={{100,-80},{140,-40}})));
Expand All @@ -94,7 +94,7 @@ block Controller "Head pressure controller"
annotation (Placement(transformation(extent={{-20,80},{0,100}})));
Buildings.Controls.OBC.ASHRAE.PrimarySystem.ChillerPlant.HeadPressure.Subsequences.MappingWithoutWSE
noWSE(
final fixSpePum=fixSpePum,
final fixSpePum=not varSpePum,
final minTowSpe=minTowSpe,
final minConWatPumSpe=minConWatPumSpe,
final minHeaPreValPos=minHeaPreValPos) if not have_WSE
Expand All @@ -109,6 +109,8 @@ block Controller "Head pressure controller"
annotation (Placement(transformation(extent={{40,-40},{60,-20}})));

protected
parameter Boolean varSpePum = not fixSpePum or have_WSE
"Flag to indicate if the plant has variable speed condenser water pumps";
Buildings.Controls.OBC.CDL.Logical.Switch swi if have_HeaPreConSig
annotation (Placement(transformation(extent={{-20,-110},{0,-90}})));
Buildings.Controls.OBC.CDL.Continuous.Sources.Constant con(
Expand Down