2.5 Check SFP presence

Introduction

This test plan is to check the functionalities of platform related software components. These software components are for managing platform hardware, including FANs, thermal sensors, SFP, transceivers, pmon, etc.

The software components for managing platform hardware on Mellanox platform is the hw-management package.

To verify that the hw-management package works as expected, the test cases need to be executed on all supported platforms:

  • Mellanox ACS-MSN2010
  • Mellanox ACS-MSN2100
  • Mellanox ACS-MSN2410
  • Mellanox ACS-MSN2700
  • Mellanox ACS-MSN2740
  • Mellanox ACS-MSN3700

The test cases are groupd in two categories:

  • Common test cases for all vendors.
  • Test cases specific for Mellanox platforms.

In common test cases, some steps are platform dependent. Detailed information will be given in the test cases.

Common Test Cases

1.1 Check platform information

Steps

  • Run show platform summary
  • Turn off/on PSU from PDU (Power Distribution Unit), run show platform psustatus respectively. In automation, PDU with programmable interface is required for turning off/on PSU. Without PDU, manual intervention required for this step.

Pass/Fail Criteria

  • show platform summary should output these fields: Platform, HwSKU, ASIC, for example:
admin@mtbc-sonic-03-2700:~$ show platform summary
Platform: x86_64-mlnx_msn2700-r0
HwSKU: ACS-MSN2700
ASIC: mellanox
  • PSU status should be OK when it is on, NOT OK when it is off. Use PDU to turn off/on PSU to verify that correct PSU status can be displayed.
admin@mtbc-sonic-03-2700:~$ show platform psustatus
PSU    Status
-----  --------
PSU 1  NOT OK
PSU 2  OK

Automation

New automation required. The step for turning on/off PSU needs programmable PDU. Need to implement a fixture for turning on/off PSU. When programmable PDU is not available in testbed, this step can only be tested manually. The fixture should be able to return information about whether this capability is supported. If not supported, skip this step in automation.

1.2 Check System EEPROM

Steps

  • Run show platform syseeprom
  • Use the platform specific eeprom.py utility to directly decode eeprom information from hardware, compare the result with output of cmd show platform syseeprom. This step is platform dependent. Different eeprom.py utility should be used on different platforms. The below example is taken from Mellanox platform.
root@mtbc-sonic-03-2700:~# python
Python 2.7.13 (default, Sep 26 2018, 18:42:22)
[GCC 6.3.0 20170516] on linux2
Type "help", "copyright", "credits" or "license" for more information.
>>> import imp
>>> m = imp.load_source('eeprom', '/usr/share/sonic/device/x86_64-mlnx_msn2740-r0/plugins/eeprom.py')
>>> t = m.board('board', '', '', '')
>>> e = t.read_eeprom()
>>> t.decode_eeprom(e)
TlvInfo Header:
   Id String:    TlvInfo
   Version:      1
   Total Length: 507
TLV Name             Code Len Value
-------------------- ---- --- -----
Product Name         0x21  64 Panther Eth 100
Part Number          0x22  20 MSN2700-CS2F
Serial Number        0x23  24 MT1533X04568
Base MAC Address     0x24   6 E4:1D:2D:F7:D5:5A
Manufacture Date     0x25  19 08/16/2015 22:28:24
Device Version       0x26   1 0
MAC Addresses        0x2A   2 2
Manufacturer         0x2B   8 Mellanox
Vendor Extension     0xFD  36
Vendor Extension     0xFD 164
Vendor Extension     0xFD  36
Vendor Extension     0xFD  36
Vendor Extension     0xFD  36
ONIE Version         0x29  21 2018.05-5.2.0004-9600
CRC-32               0xFE   4 0x371DD10F

>>>

Pass/Fail Criteria

  • The syseeprom information should have format as the example:
admin@mtbc-sonic-03-2700:~$ show platform syseeprom
TlvInfo Header:
   Id String:    TlvInfo
   Version:      1
   Total Length: 507
TLV Name             Code Len Value
-------------------- ---- --- -----
Product Name         0x21  64 Panther Eth 100
Part Number          0x22  20 MSN2700-CS2F
Serial Number        0x23  24 MT1533X04568
Base MAC Address     0x24   6 E4:1D:2D:F7:D5:5A
Manufacture Date     0x25  19 08/16/2015 22:28:24
Device Version       0x26   1 0
MAC Addresses        0x2A   2 2
Manufacturer         0x2B   8 Mellanox
Vendor Extension     0xFD  36
Vendor Extension     0xFD 164
Vendor Extension     0xFD  36
Vendor Extension     0xFD  36
Vendor Extension     0xFD  36
ONIE Version         0x29  21 2018.05-5.2.0004-9600
CRC-32               0xFE   4 0x371DD10F

(checksum valid)
  • The syseeprom info output from cmd show platform syseeprom should comply with the info decoded using platform specific eeprom.py utility.

Automation

Covered by existing automation

1.3 Run the Sensors automation

Steps

  • Run the sensors automation to ensure that it PASS.
$ ansible-playbook test_sonic.yml -i inventory --limit ${SWITCH}-${TOPO} -e testbed_name=${SWITCH}-${TOPO} -e testbed_type=${TOPO} -e testcase_name=sensors -vvvvv

For example:

$ ansible-playbook test_sonic.yml -i inventory --limit mtbc-sonic-03-2700-t0 -e testbed_name=mtbc-sonic-03-2700-t0 -e testbed_type=t0 -e testcase_name=sensors -vvvvv

Pass/Fail Criteria

The script should PASS

Automation

Covered by existing automation. In the future, this script could be converted to pytest based code.

1.4 Check SFP status and configure SFP

This case is to use the sfputil tool and show command to check SFP status and configure SFP. Currently the the only configuration is to reset SFP.

  • sfputil show presence
  • show interface transceiver presence
  • sfputil show eeprom
  • show interface transceiver eeprom
  • sfputil reset <interface name>

Steps

  • Get the list of connected ports from ansible/files/lab_connection_graph.xml, all connected ports need to be checked.
  • Use the sfputil show presence and show interface transceiver presence commands to check presence of ports.
  • Use the sfputil show eeprom and show interface transceiver eeprom commands to check eeprom information of ports.
  • Use the sfputil reset <interface name> command to reset each port.
  • Use the show interface status and show interface portchannel commands to check interface and port channel status against current topology.

Pass/Fail Criteria

  • Both sfputil show presence and show interface transceiver presence should list presence of all connected ports, for example:
admin@mtbc-sonic-03-2700:~$ sudo sfputil show presence
Port         Presence
-----------  ----------
Ethernet0    Present
Ethernet4    Present
Ethernet8    Present
Ethernet12   Present
...
  • Both sfputil show eeprom and show interface transceiver eeprom should output eeprom information of all connected ports. For each port, eeprom information should have format as the example:
admin@mtbc-sonic-03-2700:~$ sudo sfputil show eeprom
Ethernet0: SFP EEPROM detected
    Connector: No separable connector
    Encoding: Unspecified
    Extended Identifier: Power Class 1(1.5W max)
    Extended RateSelect Compliance: QSFP+ Rate Select Version 1
    Identifier: QSFP+
    Length Cable Assembly(m): 1
    Nominal Bit Rate(100Mbs): 255
    Specification compliance:
        10/40G Ethernet Compliance Code: 40GBASE-CR4
    Vendor Date Code(YYYY-MM-DD Lot): 2018-08-24
    Vendor Name: Mellanox
    Vendor OUI: 00-02-c9
    Vendor PN: MCP1600-E001
    Vendor Rev: A3
    Vendor SN: MT1834VS04288

...
  • The sfputil reset <interface name> command should be successful without error.
admin@mtbc-sonic-03-2700:~$ sudo sfputil reset Ethernet0
Resetting port Ethernet0...  OK
  • Verify that interface status is not affected after reading of EEPROM. Up and down status of interfaces and port channels should comply with current topology.

Automation

New automation required

1.5 Check xcvrd information in DB

This test case is to verify that xcvrd works as expected by checking transcever information in DB.

Steps

  • Get the list of connected ports from ansible/files/lab_connection_graph.xml, all connected ports need to be checked.
  • Check whether transceiver information of all ports are in redis: redis-cli -n 6 keys TRANSCEIVER_INFO*
  • Check detailed transceiver information of each connected port, for example: redis-cli -n 6 hgetall "TRANSCEIVER_INFO|Ethernet0"
  • Check whether TRANSCEIVER_DOM_SENSOR of all ports in redis: redis-cli -n 6 keys TRANSCEIVER_DOM_SENSOR*
  • Check detailed TRANSCEIVER_DOM_SENSOR information of each connected ports for example: redis-cli -n 6 hgetall "TRANSCEIVER_DOM_SENSOR|Ethernet0"

Pass/Fail Criteria

  • Ensure that transceiver information of all ports are in redis
admin@mtbc-sonic-03-2700:~$ redis-cli -n 6 keys TRANSCEIVER_INFO*
 1) "TRANSCEIVER_INFO|Ethernet16"
 2) "TRANSCEIVER_INFO|Ethernet84"
 3) "TRANSCEIVER_INFO|Ethernet40"
 4) "TRANSCEIVER_INFO|Ethernet44"
...
  • Ensure that detailed transceiver information of a port should be like this example:
admin@mtbc-sonic-03-2700:~$ redis-cli -n 6 hgetall "TRANSCEIVER_INFO|Ethernet0"
 1) "type"
 2) "QSFP+"
 3) "hardwarerev"
 4) "A3"
 5) "serialnum"
 6) "MT1834VS04288"
 7) "manufacturename"
 8) "Mellanox"
 9) "modelname"
10) "MCP1600-E001"
  • Ensure that TRANSCEIVER_DOM_SENSOR of all ports are in redis:
admin@mtbc-sonic-03-2700:~$ redis-cli -n 6 keys TRANSCEIVER_DOM_SENSOR*
 1) "TRANSCEIVER_DOM_SENSOR|Ethernet104"
 2) "TRANSCEIVER_DOM_SENSOR|Ethernet88"
 3) "TRANSCEIVER_DOM_SENSOR|Ethernet80"
 4) "TRANSCEIVER_DOM_SENSOR|Ethernet120"
...
  • Ensure that detailed TRANSCEIVER_DOM_SENSOR information of a port should be like this example:
admin@mtbc-sonic-03-2700:~$ redis-cli -n 6 hgetall "TRANSCEIVER_DOM_SENSOR|Ethernet0"
 1) "temperature"
 2) "0.0000"
 3) "voltage"
 4) "0.0000"
 5) "rx1power"
 6) "-inf"
 7) "rx2power"
 8) "-inf"
 9) "rx3power"
10) "-inf"
11) "rx4power"
12) "-inf"
13) "tx1bias"
14) "0.0000"
15) "tx2bias"
16) "0.0000"
17) "tx3bias"
18) "0.0000"
19) "tx4bias"
20) "0.0000"
21) "tx1power"
22) "N/A"
23) "tx2power"
24) "N/A"
25) "tx3power"
26) "N/A"
27) "tx4power"
28) "N/A"

Automation

New automation required

1.6 Sequential syncd/swss restart

Steps

  • Restart the syncd and swss service:
    • sudo service syncd restart
    • sudo service swss restart
  • After restart, check:
    • status of services: syncd, swss
      • sudo systemctl status syncd
      • sudo systemctl status swss
    • status of hw-management - Mellanox specific
      • sudo systemctl status hw-management
    • status of interfaces and port channels
      • show interface status
      • show interface portchannel
    • status of transceivers
      • show interface transcever presence
      • redis-cli -n 6 keys TRANSCEIVER_INFO*

Pass/Fail Criteria

  • After restart, status of services, interfaces and transceivers should be normal:
    • Services syncd and swss should be active(running)
    • Service hw-management should be active(exited) - Mellanox specific
    • All interface and port-channel status should comply with current topology.
    • All ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.

Automation

New automation required

1.7 Reload configuration

Steps

  • Reload configuration using: config load_minigraph -y and config reload -y
  • After reload, check:
    • status of services: syncd, swss
      • sudo systemctl status syncd
      • sudo systemctl status swss
    • status of hw-management - Mellanox specific
      • sudo systemctl status hw-management
    • status of interfaces and port channels
      • show interface status
      • show interface portchannel
    • status of transceivers
      • show interface transcever presence
      • redis-cli -n 6 keys TRANSCEIVER_INFO*

Pass/Fail Criteria

  • After reload, status of services, interfaces and transceivers should be normal:
    • Services syncd and swss should be active(running)
    • Service hw-management should be active(exited) - Mellanox specific
    • All interface and port-channel status should comply with current topology.
    • All ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.

Automation

Partly covered by existing automation. New automation required.

1.8 COLD/WARM/FAST/POWER OFF/WATCHDOG reboot

Steps

  • Perform cold/warm/fast/power off/watchdog reboot
    • cold/warm/fast reboot
      • Make use of commands to reboot the switch
    • watchdog reboot
      • Make use of new platform api to reboot the switch
    • power off reboot
      • Make use of PDUs to power on/off DUT.
      • Power on/off the DUT for (number of PSUs + 1) * 2 times
        • Power on each PSU solely
        • Power on all the PSUs simultaneously
        • Delay 5 and 15 seconds between powering off and on in each test
  • After reboot, check:
    • status of services: syncd, swss
      • sudo systemctl status syncd
      • sudo systemctl status swss
    • reboot cause:
      • show reboot-cause
    • status of hw-management - Mellanox specific
      • sudo systemctl status hw-management
    • status of interfaces and port channels
      • show interface status
      • show interface portchannel
    • status of transceivers
      • show interface transcever presence
      • redis-cli -n 6 keys TRANSCEIVER_INFO*
  • Check dmesg

Pass/Fail Criteria

  • After reboot, status of services, interfaces and transceivers should be normal:
    • Services syncd and swss should be active(running)
    • Reboot cause should be correct
    • Service hw-management should be active(exited) - Mellanox specific
    • All interface and port-channel status should comply with current topology.
    • All transcevers of ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.
  • Verify that there is no error in dmesg

Automation

Partly covered by existing automation:

  • ansible/roles/test/tasks/reboot.yml
  • ansible/roles/test/tasks/warm-reboot.yml
  • ansible/roles/test/tasks/fast-reboot.yml

Need to re-implement these scripts in pytest and cover the testing in this test case.

1.9 Check thermal sensors output using new OPTIC cables

Steps

  • Plug in new OPTIC cables
  • Check the thermal sensors output using command redis-cli -n 6 hgetall "TRANSCEIVER_DOM_SENSOR|Ethernet0". Replace 'Ethernet0' in the example with actual interface name.

Pass/Fail Criteria

  • Verify that the thermal sensors could properly detect temperature.

Automation

Manual intervention required, not automatable

1.10 Manually plug in and pull out PSU modules

This test case needs to frequently check various status, the status to be checked and commands for checking them:

  • status of services: syncd, swss:
    • systemctl status syncd
    • systemctl status swss
  • status of service: hw-management - Mellanox specific
    • systemctl status hw-management
  • status of interfaces and port channels
    • show interface status
    • show interface portchannel
  • status of transceivers
    • show interface transcever presence
    • redis-cli -n 6 keys TRANSCEIVER_INFO*
  • CPU and memory usage: top

Expected results of checking varous status:

  • Services syncd and swss should be active(running)
  • Service hw-management should be active(exited) - Mellanox specific
  • All interface and port-channel status should comply with current topology.
  • All transcevers of ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.
  • Average CPU and memory usage should be at the same level before and after the manual intervention.

Steps

  • Check PSU status using command show platform psustatus
  • Check various status.
  • Pull out one of the PSU if there are multiple PSU modules available.
  • Check PSU status using command show platform psustatus
  • Check various status.
  • Plug in the PSU module again
  • Check PSU status using command show platform psustatus
  • Check various status.
  • Repeat the test on the other PSU module.

Pass/Fail Criteria

  • Verify that command show platform psustatus can correctly indicate the current PSU status.
  • Verify that various status are expected after manual intervention. Please refer to the test case description for detailed command for checking status and expected results.

Automation

Manual intervention required, not automatable

1.11 Manually plug in and pull out PSU power cord

This test case needs to frequently check various status, the status to be checked and commands for checking them:

  • status of services: syncd, swss:
    • systemctl status syncd
    • systemctl status swss
  • status of service: hw-management - Mellanox specific
    • systemctl status hw-management
  • status of interfaces and port channels
    • show interface status
    • show interface portchannel
  • status of transceivers
    • show interface transcever presence
    • redis-cli -n 6 keys TRANSCEIVER_INFO*
  • CPU and memory usage: top

Expected results of checking varous status:

  • Services syncd and swss should be active(running)
  • Service hw-management should be active(exited) - Mellanox specific
  • All interface and port-channel status should comply with current topology.
  • All transcevers of ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.
  • Average CPU and memory usage should be at the same level before and after the manual intervention.

Steps

  • Check PSU status using command show platform psustatus
  • Check various status.
  • Pull out power cord from one of the PSU if there are multiple PSU modules available.
  • Check PSU status using command show platform psustatus
  • Check various status.
  • Plug in the power cord.
  • Check PSU status using command show platform psustatus
  • Check various status.
  • Repeat the test on the other PSU module

Pass/Fail Criteria

  • Verify that command show platform psustatus can correctly indicate the current PSU status.
  • Verify that various status are expected after manual intervention. Please refer to the test case description for detailed command for checking status and expected results.

Automation

Manual intervention required, not automatable

1.12 Manually plug in and pull out FAN modules

This test case needs to frequently check various status, the status to be checked and commands for checking them:

  • status of services: syncd, swss:
    • systemctl status syncd
    • systemctl status swss
  • status of service: hw-management - Mellanox specific
    • systemctl status hw-management
  • status of interfaces and port channels
    • show interface status
    • show interface portchannel
  • status of transceivers
    • show interface transcever presence
    • redis-cli -n 6 keys TRANSCEIVER_INFO*
  • CPU and memory usage: top

Expected results of checking varous status:

  • Services syncd and swss should be active(running)
  • Service hw-management should be active(exited) - Mellanox specific
  • All interface and port-channel status should comply with current topology.
  • All transcevers of ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) should present.
  • Average CPU and memory usage should be at the same level before and after the manual intervention.

Steps

  • Check FAN status using command show environment or sensors
  • Check various status.
  • Pull out a FAN module if there are multiple FAN modules available.
  • Check FAN status using command show environment or sensors
  • Check various status.
  • Plug in the FAN module back.
  • Check FAN status using command show environment or sensors
  • Check various status.
  • Repeat the test on another FAN module

Pass/Fail Criteria

  • Verify that command show environment or sensors can get correct FAN status and FAN speed
  • Verify that various status are expected after manual intervention. Please refer to the test case description for detailed command for checking status and expected results.

Automation

Manual intervention required, not automatable

1.13 Manually plug in and pull out optical cables

This test case needs to frequently check various status, the status to be checked and commands for checking them:

  • status of services: syncd, swss:
    • systemctl status syncd
    • systemctl status swss
  • status of service: hw-management - Mellanox specific
    • systemctl status hw-management
  • status of interfaces and port channels
    • show interface status
    • show interface portchannel
  • status of transceivers
    • show interface transcever presence
    • redis-cli -n 6 keys TRANSCEIVER_INFO*
  • CPU and memory usage: top

Expected results of checking varous status:

  • Services syncd and swss should be active(running)
  • Service hw-management should be active(exited) - Mellanox specific
  • All interface and port-channel status should comply with current topology and hardware availability:
    • When cable is unplugged, interface should be down. If the interface was the last one in port channel, the port channel should be down as well.
    • After cable is plugged in, interface should be up. If the interface was in port channel, the port channel should be up as well.
  • Transcevers of ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) and unplugged should present. Transcever of cable unplugged port should be not present.
  • Average CPU and memory usage should be at the same level before and after the manual intervention.

Steps

  • Check various status.
  • Pull out an optical cable.
  • Check various status.
  • Plug in the optical cable back.
  • Check various status.

Pass/Fail Criteria

  • Verify that after an interface is pulled out, the corresponding interface is down.
  • Verify that after the interface is plugged back, the corresponding interface should recover automatically.
  • Verify that syncd, swss and hw-management services are not affected.
  • Verify that CPU and memory usage are at the same level before and after the manual intervention.

Automation

Manual intervention required, not automatable

1.14 Check platform daemon status

This test case will check the all daemon running status inside pmon(ledd no included) if they are supposed to to be running on this platform.

  • Using command docker exec pmon supervisorctl status | grep {daemon} to get the status of the daemon

Expected results of checking daemon status:

  • the status of the daemon should be RUNNING

Steps

  • Get the running daemon list from the configuration file /usr/share/sonic/device/{platform}/{hwsku}/pmon_daemon_control.json
  • Check all the daemons running status in the daemon list

Pass/Fail Criteria

  • All the daemon status in the list shall be RUNNING

Mellanox Specific Test Cases

2.1 Ensure that the hw-management service is running properly

Steps

  • Check service status using systemctl status hw-management.
  • Check the thermal control daemon: ps -ef | grep therma-control
  • Check thermal control status: cat /var/run/hw-management/config/suspend
  • Check fan speed setting: cat /var/run/hw-management/thermal/pwm1
  • Check dmesg

Pass/Fail Criteria

  • The hw-management service should be active and exited.
admin@mtbc-sonic-01-2410:~$ sudo systemctl status hw-management
● hw-management.service - Thermal control and chassis management for Mellanox systems
   Loaded: loaded (/lib/systemd/system/hw-management.service; disabled; vendor preset: enabled)
   Active: active (exited) since Wed 2019-04-10 02:04:29 UTC; 4h 14min ago
 Main PID: 362 (code=exited, status=0/SUCCESS)
    Tasks: 2 (limit: 4915)
   Memory: 222.3M
      CPU: 5.001s
   CGroup: /system.slice/hw-management.service
           ├─2667 /bin/bash /usr/bin/hw-management-thermal-control.sh 1 8 2
           └─3434 /bin/sleep 60

Apr 10 02:04:21 mtbc-sonic-01-2410 systemd[1]: Starting Thermal control and chassis management for Mellanox systems...
Apr 10 02:04:29 mtbc-sonic-01-2410 systemd[1]: Started Thermal control and chassis management for Mellanox systems.
Apr 10 02:07:07 mtbc-sonic-01-2410 sh[362]: Mellanox thermal control is started.
Apr 10 02:08:08 mtbc-sonic-01-2410 sh[362]: ASIC thermal zone is disabled due to thermal algorithm is suspend.
Apr 10 02:08:08 mtbc-sonic-01-2410 sh[362]: Set fan speed to 60% percent.
Apr 10 02:08:08 mtbc-sonic-01-2410 sh[362]: Thermal algorithm is manually suspend..
  • The thermal control daemon should be running:
admin@mtbc-sonic-03-2700:~$ ps -ef | grep thermal-control
root 1807 1 0 02:30 ? 00:00:01 /bin/bash /usr/bin/hw-management-thermal-control.sh 1 8 2
  • Verify that currently thermal control is suspended on SONiC:
admin@mtbc-sonic-03-2700:~$ cat /var/run/hw-management/config/suspend
1
  • Verify that fan speed is set to default 60%. 153/255 = 60%
admin@mtbc-sonic-03-2700:~$ cat /var/run/hw-management/thermal/pwm1
153
  • Verify that there is no error in dmesg

Automation

New automation Required

2.2 Check SFP using ethtool

Steps

  • Use the ethtool to check SFP information, for example ethtool -m sfp1. All ports specified in lab connection graph (ansible/files/lab_connection_graph.xml) must be checked.
  • Check interface status using show interface status.

Pass/Fail Criteria

  • The ethtool should be able to read information from eeprom of SFP, for example:
admin@mtbc-sonic-03-2700:~$ sudo ethtool -m sfp1
    Identifier                                : 0x0d (QSFP+)
    Extended identifier                       : 0x00
    Extended identifier description           : 1.5W max. Power consumption
    Extended identifier description           : No CDR in TX, No CDR in RX
    Extended identifier description           : High Power Class (> 3.5 W) not enabled
    Connector                                 : 0x23 (No separable connector)
    Transceiver codes                         : 0x88 0x00 0x00 0x00 0x00 0x00 0x00 0x00
    Transceiver type                          : 40G Ethernet: 40G Base-CR4
    Transceiver type                          : 100G Ethernet: 100G Base-CR4 or 25G Base-CR CA-L
    Encoding                                  : 0x00 (unspecified)
    BR, Nominal                               : 25500Mbps
    Rate identifier                           : 0x00
    Length (SMF,km)                           : 0km
    Length (OM3 50um)                         : 0m
    Length (OM2 50um)                         : 0m
    Length (OM1 62.5um)                       : 0m
    Length (Copper or Active cable)           : 1m
    Transmitter technology                    : 0xa0 (Copper cable unequalized)
    Attenuation at 2.5GHz                     : 3db
    Attenuation at 5.0GHz                     : 5db
    Attenuation at 7.0GHz                     : 6db
    Attenuation at 12.9GHz                    : 9db
    Vendor name                               : Mellanox
    Vendor OUI                                : 00:02:c9
    Vendor PN                                 : MCP1600-E001
    Vendor rev                                : A3
    Vendor SN                                 : MT1834VS04288
    Revision Compliance                       : SFF-8636 Rev 2.0
    Module temperature                        : 0.00 degrees C / 32.00 degrees F
    Module voltage                            : 0.0000 V
  • Verify that interface status is not affected after reading of EEPROM. Up and down status of interfaces should comply with current topology design.

Automation

New automation required

2.3 Check SYSFS

Steps

  • Check ASIC temperature: cat /var/run/hw-management/thermal/asic
  • Check current FAN speed: cat /var/run/hw-management/thermal/fan1_speed_get
  • Check FAN speed setting: cat /var/run/hw-management/thermal/pwm1
  • Check other symbolic links under /var/run/hw-management/thermal

Pass/Fail Criteria

  • Verify that symbolic links are created under /var/run/hw-management. Ensure that there are no invalid symbolic link
  • Check current FAN speed against max and min fan speed, also check the the fan speed tolerance, insure it's in the range
  • Check thermal valules(CPU, SFP, PSU,...) against the max and min value to make sure they are in the range.

Automation

New automation required

2.4 Verify that /var/run/hw-management is mapped to docker pmon

Steps

  • Go to docker pmon: docker exec -it pmon /bin/bash
  • Go to /var/run of docker container, verify that host directory /var/run/hw-management is mapped to docker pmon

Pass/Fail Criteria

  • Host directory /var/run/hw-management should be mapped to docker pmon

Automation

New automation required

2.5 Check SFP presence

Steps

  • Get all the connected interfaces
  • Check the presence of the SFP on each interface and corss check the SFP status from the sysfs

Pass/Fail Criteria

  • All th SFP shall be presence and SFP status shall be OK.

Steps

  • Go to docker pmon: docker exec -it pmon /bin/bash
  • Go to /var/run of docker container, verify that host directory /var/run/hw-management is mapped to docker pmon

Pass/Fail Criteria

  • Host directory /var/run/hw-management should be mapped to docker pmon

Automation

New automation required

Automation Design

This section outlines the design of scripts automating the SONiC platform test cases. The new pytest-ansible framework will be used. Sample code can be found here.

Folder Structure and Script Files

The pytest framwork supports flexible test discovery. The plan is to put all platform related scripts under tests/platform. Command like pytest tests/platform would be able to discover all test_*.py and *_test.py under tests/platform. No entry script is required.

The folder structure and sript files:

sonic-mgmt
|-- ansible
|-- tests
    |-- platform
        |-- psu_controller.py
        |-- test_platform_info.py
        |-- test_sfp.py
        |-- test_xcvr_info_in_db.py
        |-- test_sequential_restart.py
        |-- test_reload_config.py
        |-- test_cold_reboot.py
        |-- test_warm_reboot.py
        |-- test_fast_reboot.py
        |-- check_critical_services.py
        |-- check_interface_status.py
        |-- check_transceiver_status.py
        |--mellanox
           |-- test_hw_management_service.py
           |-- test_check_sfp_using_ethtool.py
           |-- test_check_sysfs.py
           |-- check_hw_mgmt_service.py
           |-- mellanox_psu_controller.py

Filename of scripts should follow this pattern:

  • All scripts for test cases should start with test_.
  • Put vendor specific test cases in dedicated folder. For example, all Mellanox specific scripts are put under subfolder "mellanox".
  • Scripts hold helper functions or classes should start with check_, or other prefix as long as it does not conflict with above two patterns.
  • The sonic-mgmt/tests/platform/psu_controller.py script has the definition of psu_controller fixture that is used in test_platform_info.py. The psu_controller fixture returns a PSU controller object for controlling the power on/off to PSUs of DUT. This script also defines the interface of PSU controller object in PsuControllerBase class. Vendor specific PSU controller must be implemented as a sublcass of PsuControllerBase and put under vendor subfolder. For example, Mellanox specific PSU controller is impelemented in sonic-mgmt/tests/platform/mellanox/mellanox_psu_controller.py.

With this convention, to run just the common test cases, use below commands:

  • py.test tests/platform/test_* <extra arguments>

To run common and mellanox specific test cases:

  • py.test tests/platform/test_* tests/platform/mellanox/test_* <extra arguments>

Please DO NOT use below commands to run tests:

  • py.test tests/platform <extra arguments> The reason is that this pattern will recursively collect all the test cases in test_*.py files under tests/platform, including vendor specific subfolders. If there are multiple vendor specific subfolders under this folder, this pattern will try to run all the common and all vendor specific test cases.

Because these scripts need to be upstreamed, community definitely will have lots of comments. To get feedback early, we can implement the scripts in two phases.

Scripts to be implemented in phase1

Test Case Script Common for all vendors?
Case 1.1 Check platform information tests/platform/test_platform_info.py Yes
Case 1.3 Check SFP status and configure SFP tests/platform/test_sfp.py Yes
Case 1.4 Check xcvrd information in DB tests/platform/test_xcvr_info_in_db.py Yes
Case 2.1 Ensure that the hw-management service is running properly tests/platform/mellanox/test_hw_management_service.py No
Case 2.2 Check SFP using ethtool tests/platform/mellanox/test_check_sfp_using_ethtool.py No
Case 2.3 Check SYSFS tests/platform/mellanox/test_check_sysfs.py No
Case 2.4 Verify that /var/run/hw-management is mapped to docker pmon tests/platform/mellanox/check_sysfs.py No

The psu_controller fixture will also be implemented in phase 1:

  • tests/platform/psu_controller.py
  • tests/platform/mellanox/mellanox_psu_controller.py

The scripts for testing sensors ansible/roles/test/tasks/sensors_check.yml simply calls ansible/roles/sonic-common/tasks/sensors_check.yml. We can conver it to pytest in the future.

Scripts to be implemented in phase 2

Test Case Script Common for all vendors?
Case 1.5 Sequential syncd/swss restart tests/platform/test_sequential_restart.py Yes
Case 1.6 Reload configuration tests/platform/test_reload_config.py Yes
Case 1.7 COLD/WARM/FAST reboot tests/platform/test_reboot.py Yes

Helper scripts

For the tasks that can be reused in testing, they can be organnized into separate helper script files check_*.py. The test case scripts can import these helper scripts and call the functions/classes defined in them.

Reusable script Purpose
check_critical_services.py Check status of critical services for eg: wss, syncd, bgp, etc. Used by the test cases testing restart/reload/reboot.
check_hw_mgmt_service.py Check status of hw-management, thermal control process, fan speed, PWM setting. Used by the test cases testing restart/reload/reboot.
check_interface_status.py Check status of interfaces. Used by the test cases testing restart/reload/reboot.
check_sysfs.py Check the symbolic links under /var/run/hw-management. Used by the test case testing SYSFS.
check_transceiver_status.py Check the status of xcvrd information in DB. Used by the test case testing xcvrd and restart/reload/reboot.

Vendor specific steps

In common test cases, some steps may be vendor specific. For these steps, we can run different code based on the vendor information derived from the hw-sku. The hw-sku information can be retrieved from minigraph facts. For example:

if sonic_asic_type in ["mellanox"]:
   do_something()
else:
   do_something_else()